| Date |
Text |
| 2017-07-26 10:09:20 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK |
| | AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT |
| | APPLICATION IS LOW. FBC 109.3 |
| | 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON |
| | BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A |
| | CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO |
| | CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC |
| | 107.2.1 |
| | 3. RISER DIAGRAM SHOWS THE WIRE TO UNIT 332 SIZED AS |
| | 1/0, WHICH HAS A CAPACITY OF 150 AMPS. THE CURRENT 175 |
| | AMP FUSES EXCEED THIS CAPACITY. PROVIDE CORRECTION. NEC |
| | 215.2, 310.15(B)(16) |
| | 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE |
| | ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA |
| | 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 |
| | 5. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES |
| | PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED |
| | INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC |
| | C405.5 |
| | 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS FOR |
| | INTERIOR LIGHTING STIPULATED IN THE FBC ENERGY CODE. |
| | FBC C405.2.2, 405.2.2.2 |
| | 7. PROVIDE CONTROL FOR THE EXHAUST FAN ON CIRCUIT C-25. |
| | CURRENTLY, THIS APPEARS TO BE WIRED FOR CONTINUOUS |
| | OPERATION. FBC MECHANICAL 405.1; FBC 107.2.1 |
| | 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 9. ALL OUTLETS IN KITCHEN ARE REQUIRED TO BE GFCI |
| | PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(2) |
| | 10. PROVIDE SHOW WINDOW OUTLET. NEC 210.62 |
| | 11. PROVIDE AUTOMATIC CONTROL OF SIGN AND SHOW WINDOW |
| | CIRCUITS PER ENERGY CODE. FBC C405.2.4 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |