Plan Review Notes
Plan Review Notes For Permit 17070822
Permit Number 17070822
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-26 10:09:20CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK
 AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT
 APPLICATION IS LOW. FBC 109.3
 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON
 BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A
 CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO
 CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC
 107.2.1
 3. RISER DIAGRAM SHOWS THE WIRE TO UNIT 332 SIZED AS
 1/0, WHICH HAS A CAPACITY OF 150 AMPS. THE CURRENT 175
 AMP FUSES EXCEED THIS CAPACITY. PROVIDE CORRECTION. NEC
 215.2, 310.15(B)(16)
 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA
 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1
 5. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES
 PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED
 INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC
 C405.5
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS FOR
 INTERIOR LIGHTING STIPULATED IN THE FBC ENERGY CODE.
 FBC C405.2.2, 405.2.2.2
 7. PROVIDE CONTROL FOR THE EXHAUST FAN ON CIRCUIT C-25.
 CURRENTLY, THIS APPEARS TO BE WIRED FOR CONTINUOUS
 OPERATION. FBC MECHANICAL 405.1; FBC 107.2.1
 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 9. ALL OUTLETS IN KITCHEN ARE REQUIRED TO BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(2)
 10. PROVIDE SHOW WINDOW OUTLET. NEC 210.62
 11. PROVIDE AUTOMATIC CONTROL OF SIGN AND SHOW WINDOW
 CIRCUITS PER ENERGY CODE. FBC C405.2.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  