| 2017-07-28 07:01:04 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070822 |
| | ADD: 124 N. DIXIE HWY. |
| | CONT: PAN AMERICAN ENGINEERING |
| | TEL: 561-254-4858 |
| | E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH |
| | E-MAIL. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JULY 28/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEETS A-1 & A-3 BOTH INDICATE THIS TO BE A |
| | MERCANTILE OCCUPANCY. DELI OR FOOD ESTABLISHMENTS WITH |
| | OCCUPANT LOADS LESS THAN 50 ARE CLASSIFIED AS A |
| | BUSINESS OCCUPANCY. 2014 FBC-B 303.1.1 SMALL BUILDINGS |
| | AND TENANT SPACES. A BUILDING OR TENANT SPACE USED FOR |
| | ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50 |
| | PERSONS SHALL BE CLASSIFIED AS GROUP B OCCUPANCY. |
| | |
| | 2)THE COVERSHEET A-1 INDICATES A NEW ADA TOILET AT 50 |
| | SQ. FT. SHEET A-2 SHOWS A MEASUREMENT BACK WALL AT 5 |
| | FOOT 10 INCHES (EXISTING). IF THE RESTROOM IS NEW THEN |
| | THE COMPLIANCE WITH 2014 EXISTING BUILDING CODE LEVEL |
| | II 701.3 COMPLIANCE IS REQUIRED. ALL NEW CONSTRUCTION |
| | ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | BUILDING. 2014 FBC-ACCESSIBILITY: |
| | 604.3.1 SIZE. |
| | 604.3.2 OVERLAP. |
| | PLEASE NOTE THERE IS EVEN A NOTE FOR THE CLEAR FLOOR |
| | SPACE AND REQUIRED OVERLAP? THE PERMIT APPLICATION |
| | INDICATES A NEW ADA RESTROOM. IF THE RESTROOM FIXTURES |
| | WERE TO BE RECONFIGURED AGAINST THE 8 FOOT WALL AND THE |
| | WATER CLOSET WERE INSTALLED FURTHEST FROM THE DOORWAY |
| | CLEARANCES COULD BE MET. |
| | |
| | 3) NEW ADA RESTROOM PLEASE SHOW COMPLIANCE FOR THE |
| | STRUCTURAL STRENGTH OF THE GRAB BARS, 2014 |
| | ACCESSIBILITY CODE, FBC SECTION 609.8. |
| | |
| | 4) THE PLANS SHOW ON SHEET A-2 A ORDER AND PICK-UP |
| | COUNTER, BUT NO HEIGHTS ARE GIVEN, PLEASE SHOW |
| | COMPLIANCE WITH : |
| | 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL BE 38 |
| | INCHES (965 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND |
| | SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. |
| | THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND |
| | THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. |
| | |
| | 5) SHEET A-2 ALSO SHOWS 10 SEATS FOR DINING, PLEASE |
| | SHOW COMPLIANCE WITH: |
| | 5) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING |
| | PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 5A)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 5B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND |
| | 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE OR HINGE SIDE CLEARANCE. |
| | |
| | 6) SUBMITTED NOA 12-0731.06 WINDOW WALL SYSTEM, THE |
| | CONTRACTOR HAS NOT IDENTIFIED ELEMENTS IN THE ASSEMBLY. |
| | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7) PLEASE NOTE THE NOA 12-0731.06 WINDOW WALL SYSTEM |
| | DOES NOT INCLUDE THE DOOR STATED IN THE TECHNICAL |
| | SHEETS. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |