Date Text
2017-07-28 07:01:042014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070822
 ADD: 124 N. DIXIE HWY.
 CONT: PAN AMERICAN ENGINEERING
 TEL: 561-254-4858
 E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH
 E-MAIL.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 28/ 2017
 ACTION: DENIED
  
 1) SHEETS A-1 & A-3 BOTH INDICATE THIS TO BE A
 MERCANTILE OCCUPANCY. DELI OR FOOD ESTABLISHMENTS WITH
 OCCUPANT LOADS LESS THAN 50 ARE CLASSIFIED AS A
 BUSINESS OCCUPANCY. 2014 FBC-B 303.1.1 SMALL BUILDINGS
 AND TENANT SPACES. A BUILDING OR TENANT SPACE USED FOR
 ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50
 PERSONS SHALL BE CLASSIFIED AS GROUP B OCCUPANCY.
  
 2)THE COVERSHEET A-1 INDICATES A NEW ADA TOILET AT 50
 SQ. FT. SHEET A-2 SHOWS A MEASUREMENT BACK WALL AT 5
 FOOT 10 INCHES (EXISTING). IF THE RESTROOM IS NEW THEN
 THE COMPLIANCE WITH 2014 EXISTING BUILDING CODE LEVEL
 II 701.3 COMPLIANCE IS REQUIRED. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING. 2014 FBC-ACCESSIBILITY:
 604.3.1 SIZE.
 604.3.2 OVERLAP.
 PLEASE NOTE THERE IS EVEN A NOTE FOR THE CLEAR FLOOR
 SPACE AND REQUIRED OVERLAP? THE PERMIT APPLICATION
 INDICATES A NEW ADA RESTROOM. IF THE RESTROOM FIXTURES
 WERE TO BE RECONFIGURED AGAINST THE 8 FOOT WALL AND THE
 WATER CLOSET WERE INSTALLED FURTHEST FROM THE DOORWAY
 CLEARANCES COULD BE MET.
  
 3) NEW ADA RESTROOM PLEASE SHOW COMPLIANCE FOR THE
 STRUCTURAL STRENGTH OF THE GRAB BARS, 2014
 ACCESSIBILITY CODE, FBC SECTION 609.8.
  
 4) THE PLANS SHOW ON SHEET A-2 A ORDER AND PICK-UP
 COUNTER, BUT NO HEIGHTS ARE GIVEN, PLEASE SHOW
 COMPLIANCE WITH :
 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL BE 38
 INCHES (965 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 5) SHEET A-2 ALSO SHOWS 10 SEATS FOR DINING, PLEASE
 SHOW COMPLIANCE WITH:
 5) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 5A)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 6) SUBMITTED NOA 12-0731.06 WINDOW WALL SYSTEM, THE
 CONTRACTOR HAS NOT IDENTIFIED ELEMENTS IN THE ASSEMBLY.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 7) PLEASE NOTE THE NOA 12-0731.06 WINDOW WALL SYSTEM
 DOES NOT INCLUDE THE DOOR STATED IN THE TECHNICAL
 SHEETS. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER