| Plan Review Notes For Permit 17070813 |
| Permit Number |
17070813 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-22 11:48:24 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070813 | | | 8/22/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M2.1: THE CORRIDORS 217 AND 233 CANNOT BE USED | | | TO CONVEY RETURN AIR BACK TO AC 231- SEE SECTION 601.2. | | | | | | 2) M2.1: THE LOUVERED MECHANICAL CLOSET DOORS SHALL BE | | | NON-COMBUSTIBLE PER SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION, AND SECTION 602.2.1 FBC-14 MECHANICAL. | | | | | | 3) M6.1: PLEASE PROVIDE EQUIPMENT SCHEDULES FOR THE | | | EXISTING AC SYSTEMS. | | | | | | 4) SHOW THE LOCATION OF THE NEW CONDENSER AND PROVIDE | | | ENGINEERING AND THE WIND LOAD DESIGN CRITERIA FOR | | | INSTALLATION- SECTION 301.15. | | | | | | 5) M2.1: VERIFY REQUIRED CLEARANCES FOR THE NEW O/A | | | INTAKES- SECTION 401.4 AND INDICATE HOW THE OPENINGS | | | WILL BE PROTECTED- SECTION 401.5. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|