Plan Review Notes
Plan Review Notes For Permit 17070809
Permit Number 17070809
Review Stop B
Sequence Number 2
Notes
Date Text
2017-08-02 16:54:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS REVIEW:
  
 1. THE DOCUMENT 68545B-SEALS HAS AN ERROR IN THE
 DIGITAL SIGNATURE, SEE SIGNATURE REVIEW.
  
 2. FROM PREVIOUS LIST - PAGE 32 REFERS TO WIND DESIGN
 160MPH, THIS PROJECT CRITERIA IS 170MPH, REVISE.
  
 **CHECK ALL PAGES. DETAIL STDTL07 ALSO SPECS 160MPH.**
  
  
  