2017-07-21 13:36:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE ADDRESS ON THE APPLICATION AND THE ADDRESS ON
 THE PLAN SHEET DO NOT MATCH.
  
 PLEASE CARIFY AND CORRECT.
  
  
  
 2) IN THE SYMBOL LEGEND THE CEILING HEIGHT IS INDICATED
 AS 0.0".
  
 PLEASE CORRECT.
  
  
 3) BOTH PENDANT AND UPRIGHT HEADS ARE INDICATED IN THE
 SPEC CALL OUT BOX.
  
 PLEASE CLARIFY IF BOTH SPRINKLER TYPES WILL BE PRESENT
 OR THE JUST THE UPRIGHTS. IF JUST THE UPRIGHTS UDER
 THIS SCOPE, REMOVE ANY REFERENCES TO PENDANTS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  