| Plan Review Notes For Permit 17070796 |
| Permit Number |
17070796 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-21 13:36:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THE ADDRESS ON THE APPLICATION AND THE ADDRESS ON | | | THE PLAN SHEET DO NOT MATCH. | | | | | | PLEASE CARIFY AND CORRECT. | | | | | | | | | | | | 2) IN THE SYMBOL LEGEND THE CEILING HEIGHT IS INDICATED | | | AS 0.0". | | | | | | PLEASE CORRECT. | | | | | | | | | 3) BOTH PENDANT AND UPRIGHT HEADS ARE INDICATED IN THE | | | SPEC CALL OUT BOX. | | | | | | PLEASE CLARIFY IF BOTH SPRINKLER TYPES WILL BE PRESENT | | | OR THE JUST THE UPRIGHTS. IF JUST THE UPRIGHTS UDER | | | THIS SCOPE, REMOVE ANY REFERENCES TO PENDANTS. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|