| Notes |
| Date |
Text |
| 2017-10-04 16:35:23 | 10/4/17 PLUMBING 2ND REVIEW*DENIED* | | | | | | COMMENTS FROM 1ST REVIEW NOT ANSWERED IN FULL OR NOT | | | ADDRESSED AT ALL. 2ND REQUEST | | | | | | 1) SUBMIT SPECIFICATION SHEETS/ INSTALLATION MANUAL FOR | | | EJECTOR PUMP AND BASIN FBC 107.2.1 | | | | | | 2) SHOW REQUIRED VALVES ON EJECTOR PUMP FBC-P3007.2 | | | | | | 3) AAV ARE NOT PERMITTED ON EJECTOR PUMP SHOW HOW YOU | | | WILL COMPLY WITH FBC-P3114.8 | | | | | | 4) EXPLAIN AND SHOW WITH DETAIL HOW YOU INTENT TO | | | CONNECTED THE EJECTOR PUMP DISCHARGE TO THE EXISTING | | | SYSTEM AND IF ANY TUNNELIING WITH BE DONE.107.2.1 |
|