| Plan Review Notes For Permit 17070787 |
| Permit Number |
17070787 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-24 14:58:00 | 1) SUBMIT SPECIFICATION SHEETS / INSTALLATION MANUAL | | | FOR EJECTOR PUMP AND BASIN | | | | | | 2) SHOW GATE VALVE AFTER CHECK VALVE ON DRAWING | | | | | | 3) SHOW AND EXPLAIN VENTING SYSTEM AND SHOW REQUIRED | | | VENT AT PUMP BASIN | | | | | | 4) REQUIRED SEPERATE ELECTRIC PERMIT FOR PUMP | | | | | | 5) PLEASE ADVISE HOW YOU WILL BE CONNECTING TO THE | | | EXISTING KITCHEN DRAIN LINE AND IF THERE WILL BE ANY | | | TUNNELING UNDER THE HOME. IF TUNNELING IS TO BE DONE | | | PLEASE SUBMIT THE FOLLOWING: | | | | | | A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE | | | SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO | | | EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED, | | | THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO | | | EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS. | | | DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED | | | THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE | | | CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND | | | BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED BELOW | | | GROUND PER THE FLORIDA BUILDING CODE, RESIDENTIAL, | | | SECTION 318 AND THE FLORIDA BUILDING CODE, BUILDING, | | | SECTION 2603.8. | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|