Plan Review Notes
Plan Review Notes For Permit 17070787
Permit Number 17070787
Review Stop P
Sequence Number 1
Notes
Date Text
2017-07-24 14:58:001) SUBMIT SPECIFICATION SHEETS / INSTALLATION MANUAL
 FOR EJECTOR PUMP AND BASIN
  
 2) SHOW GATE VALVE AFTER CHECK VALVE ON DRAWING
  
 3) SHOW AND EXPLAIN VENTING SYSTEM AND SHOW REQUIRED
 VENT AT PUMP BASIN
  
 4) REQUIRED SEPERATE ELECTRIC PERMIT FOR PUMP
  
 5) PLEASE ADVISE HOW YOU WILL BE CONNECTING TO THE
 EXISTING KITCHEN DRAIN LINE AND IF THERE WILL BE ANY
 TUNNELING UNDER THE HOME. IF TUNNELING IS TO BE DONE
 PLEASE SUBMIT THE FOLLOWING:
  
 A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE
 SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO
 EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED,
 THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO
 EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS.
 DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED
 THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE
 CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND
 BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED BELOW
 GROUND PER THE FLORIDA BUILDING CODE, RESIDENTIAL,
 SECTION 318 AND THE FLORIDA BUILDING CODE, BUILDING,
 SECTION 2603.8.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  