| Plan Review Notes For Permit 17070785 |
| Permit Number |
17070785 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-21 14:18:13 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | ONLY ONE (1) SET OF SMALL DRAWINGS BROUGHT IN FOR | | | REVIEW | | | | | | PLEASE LIST TYPE OF FUEL IN TANK. | | | | | | NEED TO DEFINE THE HAZARDOUS LOCATION AT AND AROUND | | | TANK PER 500.4(A). | | | | | | VEEDEROOT CONDUIT LOOKS TO BE IN THE HAZARDOUS | | | LOCATION. | | | | | | |
|