2017-07-27 14:26:151ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070748
 7/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVIEW SECTION C408.2.1 FBC-14 ENERGY
 CONSERVATION COMMISSIONING PLAN PRINTED BELOW, AND
 RESUBMIT IN ACCORDANCE WITH ITEMS #1-5.
  
 C408.2.1 COMMISSIONING PLAN.
 A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED
 DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL
 INCLUDE THE FOLLOWING ITEMS:
  
 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL
 BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
 INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF
 THE ACTIVITIES.
  
 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
 SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO
 BE PERFORMED.
  
 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED
 TO CALIBRATIONS AND ECONOMIZER CONTROLS.
  
 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
 AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER
 DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
  
 5. MEASURABLE CRITERIA FOR PERFORMANCE
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER