| Plan Review Notes For Permit 17070744 |
| Permit Number |
17070744 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-11 14:16:15 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070744 | | | 8/11/17 | | | | | | COMMENTS FROM THE 1ST REVIEW STILL EXISTS- SEE BELOW. | | | | | | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17070744 | | | 7/25/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN- | | | SECTION 107.2.1 WPB AMENDMENTS TO THE FBC | | | | | | 2) SUBMIT AN AHRI CERTIFICATE FOR THE NEW SYSTEM- | | | SECTION R101.4.7 FBC-14 ENERGY CONSERVATION | | | | | | 3) PROVIDE AC COOLING AND HEATING SIZING CALCULATIONS- | | | SECTION R403.6.1 | | | | | | 4) REFER TO SECTION R101.4.5: CHANGE IN SPACE | | | CONDITIONING. | | | ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME | | | CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO | | | FULL COMPLIANCE WITH THIS CODE- SEE SECTION R101.5.1 | | | AND SUBMIT AN ENERGY COMPLIANCE FORM. | | | | | | 5) PROVIDE DETAILS FOR INSTALLATION OF THE NEW AC PAD | | | AND TIE DOWN OF THE CONDENSER- SECTIONS M1305.1.4.1 & | | | M1401.4 FBC-14 RESIDENTIAL. | | | | | | 6) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION M1411. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|