| 2017-09-06 12:26:46 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070703 | | | 9/6/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1: THE REQUIRED MAKEUP AIR FOR THE OVEN | | | EXHAUST CANNOT REDUCE THE REQUIRED RATE OF OUTDOOR | | | AIRFLOW TO THE BREATHING ZONE IN THE OCCUPIED SPACES OF | | | THE COFFEE SHOP- SECTION 403.3. PLEASE PROVIDE MAKEUP | | | AIR AT A RATE APROXIMATELY EQUAL TO THE AMOUNT OF | | | EXHAUST AIR REQUIRED- SECTION 508.1. | | | | | | 2) SHOW HOW THE EXHAUST FAN WILL BE OPERATE | | | AUTOMATICALLY WHEN THE OVEN IS IN USE- SECTION 507.1. | | | | | | 3) THE SUBMITTED SPECS FOR THE BROAN EXHAUST FAN APPEAR | | | TO INDICATE THE FAN IS FOR RESIDENTIAL USE, AND HAS NOT | | | BEEN APPROVED TO EXHAUST A COMMERCIAL COOKING OVEN- | | | 506.5. | | | | | | 4) VERIFY THAT THE OVEN EXHAUST WILL TERMINATE NO LESS | | | THAN 30" ABOVE THE ADJOINING ROOF- SECTION 506.4.2. | | | | | | 5) THE SUBMITTED SPECS FOR THE OVEN DO NOT INDICATE THE | | | APPLIANCE IS LISTED AND LABELED IN ACCORDANCE WITH | | | UL-197. SEE SECTION 917.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|