2017-09-06 12:26:462ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070703
 9/6/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: THE REQUIRED MAKEUP AIR FOR THE OVEN
 EXHAUST CANNOT REDUCE THE REQUIRED RATE OF OUTDOOR
 AIRFLOW TO THE BREATHING ZONE IN THE OCCUPIED SPACES OF
 THE COFFEE SHOP- SECTION 403.3. PLEASE PROVIDE MAKEUP
 AIR AT A RATE APROXIMATELY EQUAL TO THE AMOUNT OF
 EXHAUST AIR REQUIRED- SECTION 508.1.
  
 2) SHOW HOW THE EXHAUST FAN WILL BE OPERATE
 AUTOMATICALLY WHEN THE OVEN IS IN USE- SECTION 507.1.
  
 3) THE SUBMITTED SPECS FOR THE BROAN EXHAUST FAN APPEAR
 TO INDICATE THE FAN IS FOR RESIDENTIAL USE, AND HAS NOT
 BEEN APPROVED TO EXHAUST A COMMERCIAL COOKING OVEN-
 506.5.
  
 4) VERIFY THAT THE OVEN EXHAUST WILL TERMINATE NO LESS
 THAN 30" ABOVE THE ADJOINING ROOF- SECTION 506.4.2.
  
 5) THE SUBMITTED SPECS FOR THE OVEN DO NOT INDICATE THE
 APPLIANCE IS LISTED AND LABELED IN ACCORDANCE WITH
 UL-197. SEE SECTION 917.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER