| 2017-07-24 09:45:20 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. A-2 WITH AN OCCUPANT LOAD OF 28 PEOPLE SEPARATE | | | FACILITIES SHALL BE PROVIDED FOR EACH SEX. PER FBC PL | | | 403.2 | | | | | | 2.THE AAV FOR THE GREASE INTERCEPTOR SHALL BE INSTALLED | | | ABOVE FLOOD LEVEL RIM OF THE HIGHEST FIXTURE SERVED. | | | PER FBC PL 918.4 | | | | | | 3. THE SAMPLE PORT SHALL NOT HAVE A SUMP ON THE BOTTOM | | | A 4" TWO WAY CLEAN OUT IS ALL THAT IS REQUIRED. | | | | | | 4. THE INLET OF THE GB 75 IS 4" THE DRAIN THAT IS | | | CONNECTED TO THE OUTLET SHALL BE 4" THE SIZE OF THE | | | DRAINAGE PIPING SHALL NOT BE REDUCED IN SIZE IN THE | | | DIRECTION OF THE FLOW. PER FBC PL 704.2 | | | | | | 5. WHAT TYPE OF COOKING WILL BE DONE AT THIS LOCATION, | | | PLEASE PROVIDE A MENU TO DETERMINE WHAT TYPE IF ANY | | | TYPE OF GREASY WASTE WILL BE PRODUCED. I NO GREASY | | | WASTE IS PRODUCED A GREASE INTERCEPTOR IS NOT REQUIRED. | | | PER FBC PL 1003.3.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|