2017-07-24 14:46:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070703
 7/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW OVEN SHALL EITHER BE PROVIDED WITH A TYPE II
 EXHAUST HOOD OR THE SPACE SHALL BE PROVIDED WITH
 EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER SQ. FT.-
 SECTION 507.2.2.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 OVEN- SECTION 917.1.
  
 3) PROVIDE AN AIR BALANCE CALCULATION.
  
 4) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 KITCHEN EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS-
 SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 5) THE REQUIRED INPUT DATA REPORT WAS NOT SUBMITTED
 ALONG WITH ENERGYGAUGE COMPLIANCE REPORT.
  