| Notes |
| Date |
Text |
| 2017-07-24 14:46:48 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070703 | | | 7/24/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE NEW OVEN SHALL EITHER BE PROVIDED WITH A TYPE II | | | EXHAUST HOOD OR THE SPACE SHALL BE PROVIDED WITH | | | EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER SQ. FT.- | | | SECTION 507.2.2. | | | | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW | | | OVEN- SECTION 917.1. | | | | | | 3) PROVIDE AN AIR BALANCE CALCULATION. | | | | | | 4) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR | | | KITCHEN EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- | | | SECTION 107.1 WPB AMENDMENTS TO THE FBC. | | | | | | 5) THE REQUIRED INPUT DATA REPORT WAS NOT SUBMITTED | | | ALONG WITH ENERGYGAUGE COMPLIANCE REPORT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|