| Date |
Text |
| 2017-07-25 11:20:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 3 - THE IS AN INCORRECT REFERENCE TO THE |
| | CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 3 - THERE IS AN INDICATION OF A HYBRID |
| | MICROWAVE OVEN. PLEASE CLARIFY THIS PIECE OF EQUIPMENT |
| | AND PROVIDE MANUFACTURERES SPEC. |
| | |
| | ADDITIONALLY, PLEASE PROVIDE A REVIEW OF THE PROPOSED |
| | TYPE OF FOOD PRODUCTS OR MENU. COMMERCIAL COOKING WITH |
| | GREASE LADEN VAPORS SHALL COMPLY WITH NFPA 96. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 3) SHEET A 3 - THERE IS INDICATIONS OF EXISTING FIRE |
| | SPRINKLERS. ANY REMODEL WORK REQUIRES AN EVALUATION OF |
| | THE SPRINKLER SYSTEM FOR CODE COMPLIANT COVERAGE. |
| | |
| | ANY WORK ON THE SPRINKLER SYSTEM SHALL BE DONE UNDER |
| | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| | CONTRACTORS. |
| | |
| | PLEASE PROVIDE A NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 3 - THE IS A DOOR INDICATED, 2 A, FROM THE |
| | WORK AREA LEADING TO THE REAR DOOR. THIS IS A DOOR IN |
| | THE MEANS OF EGRESS ACCORDING TO THE LIFE SAFETY PLAN. |
| | |
| | THE DOOR SCHEDULE DOES NOT INDICATE ANY HARDWARE, LOCKS |
| | OR LATCHES FOR THIS DOOR. THE HARDWARE, LOCKS AND |
| | LATCHES SHALL COMPLY WITH NFPA 101, CHAPTER 7, MEANS OF |
| | EGRESS. |
| | |
| | PLEASE PROVIDE DETAILS AS APPLICABLE THAT MEET THE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 5) SHEET E 1 - THERE ARE NO INDICATIONS OF FIRE ALARM |
| | EQUIPMENT/DEVICES. ANY REMODEL WORK REQUIRES AN |
| | EVALUATION OF ANY EXISIING FIRE ALARM SYSTEM DEVICES. |
| | |
| | ANY WORK ON THE ALARM SYSTEM SHALL BE DONE UNDER |
| | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| | CONTRACTORS. |
| | |
| | PLEASE PROVIDE A NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |