| 2017-07-25 14:58:01 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| | 250.94, 408.30 |
| | 2. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24. |
| | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS FROM MAIN SERVICE (FOR ENTIRE BUILDING) FEEDING |
| | THIS UNIT TO CONFIRM THE CURRENT SERVICE SIZE IS |
| | ADEQUATE. NEC 220, 215.5, 215.2; FBC 107.2.1 |
| | 4. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES |
| | PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED |
| | INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC |
| | C405.5 |
| | 5. ALL RECEPTACLES IN KITCHEN/WORK AREA AND WITHIN 6 |
| | FEET OF A SINK MUST BE GFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.8(B)(2),(5) |
| | 6. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| | CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. |
| | NEC 110.10 |
| | 7. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW |
| | OUTLETS PER FBC ENERGY CODE. FBC C405.2.4 |
| | 8. PROVIDE AUTOMATIC LIGHTING CONTROL FOR LIGHTS OVER |
| | COUNTER ON CIRCUIT C36. FBC C405.2.2 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |