| Plan Review Notes For Permit 17070687 |
| Permit Number |
17070687 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-01 13:36:11 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) SUBMIT TWO COMPLETE SETS OF STRUCTURAL, PLUMBING AND | | | ELECTRICAL PLANS. PLANS SHALL SHOW COMPLIANCE WITH POOL | | | BARRIER REQUIREMENTS AND FBC ENERGY CONSERVATION. FBC | | | 107.1 | | | | | | 3) A POOL ELECTRICAL PERMIT APPLICATION IS REQUIRED TO | | | BE SUBMITTED BEFORE THE POOL PERMIT CAN BE ISSUED. | | | |
|