Plan Review Notes
Plan Review Notes For Permit 17070684
Permit Number 17070684
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-26 15:10:36CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COPY OF CONTRACT WITH SCOPE OF WORK AND
 VALUE LISTED. FBC 109.3
 2. NOTE 1 ON SHEET E-1 REFERENCES THE 2008 NEC. PROVIDE
 CORRECTION. FBC PREFACE.
 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 4. PROVIDE LIGHT FIXTURE SCHEDULE AND SYMBOL LEGEND.
 FBC 107.2.1, NEC 110.3
 5. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 6. LIGHTING IN BATHTUB OR SHOWER AREAS, AND EXTERIOR
 AREAS, SHALL BE SUITABLE FOR DAMP LOCATIONS. PROVIDE
 CORRECTION. NEC 410.10(D); FBC RE4003.11
 7. PROVIDE GFCI PROTECTION FOR OUTLET IN LAUNDRY WITHIN
 6 FEET OF SINK. NEC 210.8; FBC RE3902.7
 8. PROVIDE GFCI OUTLETS TO CODE IN KITCHEN. NEC 210.8,
 210.52; FBC RE3901.4, FBC 107.2.1
 9. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. PROVIDE COMPLIANCE. NEC 210.12; FBC
 RE3902.12
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 11. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. CURRENTLY, BOTH PANELS SHOW THE SAME AMPERE
 LOAD, WHICH IS IMPOSSIBLE SINCE PANEL B IS FED FROM
 PANEL A. NEC 220; FBC RE3602.3
 12. PANEL A IS SHOWN AS A MAIN LUG ONLY PANEL IN THE
 PANEL SCHEDULE, AND DOES NOT SHOW A MAIN AHEAD OF THIS
 PANEL IN THE RISER DIAGRAM. IF THIS IS ACCURATE, THIS
 PANEL WOULD BE LIMITED TO A MAXIMUM OF SIX BREAKERS.
 PROVIDE CORRECTION AND/OR CLARIFICATION. FBC 107.2.1;
 NEC 230.71
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  