Plan Review Notes
Plan Review Notes For Permit 17070680
Permit Number 17070680
Review Stop M
Sequence Number 1
Notes
Date Text
2017-07-25 12:01:431ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070680
 7/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A MORE COMPREHENSIVE MECHANICAL PLAN
 SHOWING ALL REQUIRED CHANGES TO THE EXISTING SYSTEM(S)
 AS A RESULT OF THE CHANGE FROM ONE TO TWO TENANT
 SPACES, AND THE INSTALLATION OF A DEMISING WALL. IT
 WOULD APPEAR BY THE SCOPE OF THE PROJECT THAT SOME
 DUCTS WOULD HAVED TO TE DEMOLISHED OR RELOCATED BECAUSE
 OF THE DEMISING WALL. SHOW THE LOCATION OF THE AIR
 HANDLER AND INDICATE HOW AIR IS BEING RETURN TO THE
 UNIT FROM BOTH TENANT SPACES- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 2) PROVIDE THE SIZE OF THE SUPPLY DUCT IN THE OFFICE
 WHERE THE 10" TRANSFER DUCT IS TO BE INSTALLED- SECTION
 601.5 EXCEPTION 1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  