| Plan Review Notes For Permit 17070680 |
| Permit Number |
17070680 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-25 12:01:43 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070680 | | | 7/25/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A MORE COMPREHENSIVE MECHANICAL PLAN | | | SHOWING ALL REQUIRED CHANGES TO THE EXISTING SYSTEM(S) | | | AS A RESULT OF THE CHANGE FROM ONE TO TWO TENANT | | | SPACES, AND THE INSTALLATION OF A DEMISING WALL. IT | | | WOULD APPEAR BY THE SCOPE OF THE PROJECT THAT SOME | | | DUCTS WOULD HAVED TO TE DEMOLISHED OR RELOCATED BECAUSE | | | OF THE DEMISING WALL. SHOW THE LOCATION OF THE AIR | | | HANDLER AND INDICATE HOW AIR IS BEING RETURN TO THE | | | UNIT FROM BOTH TENANT SPACES- SECTION 107.2.1 WPB | | | AMENDMENTS TO THE FBC. | | | | | | 2) PROVIDE THE SIZE OF THE SUPPLY DUCT IN THE OFFICE | | | WHERE THE 10" TRANSFER DUCT IS TO BE INSTALLED- SECTION | | | 601.5 EXCEPTION 1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|