2017-09-29 14:09:51600 OKEECHOBEE BOULEVARD
 PERMIT #17070653
 REVIEW COMMENTS - FIRE DEPT.
  
 REPEAT COMMENT - PLANS INDICATE A DEDICATED WATER LINE
 WITH TAMPER SWITCH IS NEEDED; HOWEVER, PLAN DOES NOT
 SHOW THE LOCATION OF THE TAMPER SWITCH OR INDICATE
 WHERE THIS WATER SUPPLY IS BEING CONNECTED (DOMESTIC?
 FIRE?).
  
 REPEAT COMMENT - PLANS INDICATE A MAXIMUM OPERATING
 PRESSURE OF 70 PSI RESIDUAL AND 125 PSI STATIC. IF
 RECEIVING WATER FROM THE WET PIPE SPRINKLER SYSTEM A
 PRESSURE REDUCING DEVICE WILL BE NEEDED AS THE SYSTEM
 PRESSURES EXCEED 125 PSI.
  