| Plan Review Notes For Permit 17070653 |
| Permit Number |
17070653 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-09-29 14:09:51 | 600 OKEECHOBEE BOULEVARD | | | PERMIT #17070653 | | | REVIEW COMMENTS - FIRE DEPT. | | | | | | REPEAT COMMENT - PLANS INDICATE A DEDICATED WATER LINE | | | WITH TAMPER SWITCH IS NEEDED; HOWEVER, PLAN DOES NOT | | | SHOW THE LOCATION OF THE TAMPER SWITCH OR INDICATE | | | WHERE THIS WATER SUPPLY IS BEING CONNECTED (DOMESTIC? | | | FIRE?). | | | | | | REPEAT COMMENT - PLANS INDICATE A MAXIMUM OPERATING | | | PRESSURE OF 70 PSI RESIDUAL AND 125 PSI STATIC. IF | | | RECEIVING WATER FROM THE WET PIPE SPRINKLER SYSTEM A | | | PRESSURE REDUCING DEVICE WILL BE NEEDED AS THE SYSTEM | | | PRESSURES EXCEED 125 PSI. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WPB FIRE RESCUE | | | [email protected] |
|