| Notes |
| Date |
Text |
| 2017-07-20 09:19:05 | 600 OKEECHOBEE BOULEVARD | | | PERMIT #17070653 | | | REVIEW COMMENTS - FIRE DEPT. | | | | | | PLANS INDICATE A DEDICATED WATER LINE WITH TAMPER | | | SWITCH IS NEEDED; HOWEVER, PLAN DOES NOT SHOW THE | | | LOCATION OF THE TAMPER SWITCH OR INDICATE WHERE THIS | | | WATER SUPPLY IS BEING CONNECTED (DOMESTIC? FIRE?). | | | | | | PLANS INDICATE A MAXIMUM OPERATING PRESSURE OF 70 PSI | | | RESIDUAL AND 125 PSI STATIC. IF RECEIVING WATER FROM | | | THE WET PIPE SPRINKLER SYSTEM A PRESSURE REDUCING | | | DEVICE WILL BE NEEDED AS THE SYSTEM PRESSURES EXCEED | | | 125 PSI. | | | | | | SUBMIT PRODUCT DATA FOR CORE SUPPRESSION SYSTEM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WPB FIRE RESCUE | | | [email protected] |
|