 PERMIT #17070653
 REVIEW COMMENTS - FIRE DEPT.
  
 PLANS INDICATE A DEDICATED WATER LINE WITH TAMPER
 SWITCH IS NEEDED; HOWEVER, PLAN DOES NOT SHOW THE
 LOCATION OF THE TAMPER SWITCH OR INDICATE WHERE THIS
 WATER SUPPLY IS BEING CONNECTED (DOMESTIC? FIRE?).
  
 PLANS INDICATE A MAXIMUM OPERATING PRESSURE OF 70 PSI
 RESIDUAL AND 125 PSI STATIC. IF RECEIVING WATER FROM
 THE WET PIPE SPRINKLER SYSTEM A PRESSURE REDUCING
 DEVICE WILL BE NEEDED AS THE SYSTEM PRESSURES EXCEED
 125 PSI.
  
 SUBMIT PRODUCT DATA FOR CORE SUPPRESSION SYSTEM.
  