| 2017-07-20 08:17:13 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070648 | | | 7/20/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AC SYSTEM IN THE CABANA NOTED AS "EXISTING" | | | APPEARS TO HAVE BEEN INSTALLED AT SOME POINT WITHOUT A | | | PERMIT. THERE ARE NO RECORDS IN THE CITY FILES OF | | | EITHER A MECHANICAL OR ELECTRICAL PERMIT BEING PULLED | | | FOR THE SYSTEMS, OR RECORD OF ANY INSPECTIONS | | | PERFORMED. FURTHER, THE PALM BEACH APPRAISORS REPORT | | | LISTS THE BUILDING AS "NO HEATING OR AC". AS A RESULT | | | THE 'EXISTING" SYSTEM SHALL BE REVIEWED AS A NEW SYSTEM | | | AND SHALL BE IN COMPLIANCE WITH THE CURRENT FLORIDA | | | BUILDING CODES. | | | | | | 2) PLEASE REVISE THE AC PLAN FOR THE COTTAGE TO INCLUDE | | | AN EQUIPMENT SCHEDULE FOR THE "EXISTING" SYSTEM, AND | | | SUBMIT AN AHRI CERTIFICATE. | | | | | | 3) REVISE THE ELECTRICAL PLANS TO INCLUDE THE | | | "EXISTING" SYSTEM. | | | | | | 4) THE CABANA SHALL BE IN FULL COMPLIANCE WITH THE | | | FLORDIA ENERGY CONSERVATION CODE. PLEASE SEE SECTION | | | R101.4.5 AND SUBMIT A COMPLIANCE FORM USING EITHER THE | | | PRESCRIPTVE FORM R402 OR THE PERFORMANCE BASED | | | COMPLIANCE SOFTWARE PRINTOUT- FORMR405 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|