2017-07-20 08:17:131ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070648
 7/20/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC SYSTEM IN THE CABANA NOTED AS "EXISTING"
 APPEARS TO HAVE BEEN INSTALLED AT SOME POINT WITHOUT A
 PERMIT. THERE ARE NO RECORDS IN THE CITY FILES OF
 EITHER A MECHANICAL OR ELECTRICAL PERMIT BEING PULLED
 FOR THE SYSTEMS, OR RECORD OF ANY INSPECTIONS
 PERFORMED. FURTHER, THE PALM BEACH APPRAISORS REPORT
 LISTS THE BUILDING AS "NO HEATING OR AC". AS A RESULT
 THE 'EXISTING" SYSTEM SHALL BE REVIEWED AS A NEW SYSTEM
 AND SHALL BE IN COMPLIANCE WITH THE CURRENT FLORIDA
 BUILDING CODES.
  
 2) PLEASE REVISE THE AC PLAN FOR THE COTTAGE TO INCLUDE
 AN EQUIPMENT SCHEDULE FOR THE "EXISTING" SYSTEM, AND
 SUBMIT AN AHRI CERTIFICATE.
  
 3) REVISE THE ELECTRICAL PLANS TO INCLUDE THE
 "EXISTING" SYSTEM.
  
 4) THE CABANA SHALL BE IN FULL COMPLIANCE WITH THE
 FLORDIA ENERGY CONSERVATION CODE. PLEASE SEE SECTION
 R101.4.5 AND SUBMIT A COMPLIANCE FORM USING EITHER THE
 PRESCRIPTVE FORM R402 OR THE PERFORMANCE BASED
 COMPLIANCE SOFTWARE PRINTOUT- FORMR405
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  