| 2017-08-16 10:56:58 | 1) THE OUTDOOR TANKLESS WATER HEATER IS NOT CONSIDERED |
| | A "DIRECT VENT UNIT" AND MUST COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION CLEARANCE REQUIREMENTS |
| | WHICH IS 48 INCHES FROM AN OPERABLE DOOR OR WINDOW. |
| | SHOW THIS ON THE COPIES OF THE SUBMITTED HOUSE PLAN |
| | SHOWING THE LOCATION OF THE TANKLESS WATER HEATER. |
| | SUBMIT TWO COPIES OF THE PAGE FROM THE MANUFACTURER'S |
| | INSTALLATION MANUAL THAT SHOWS THE CLEARANCES FOR |
| | NON-DIRECT VENT UNIT. |
| | 2) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| | G2412.8, G2413.1, G2413.2, & G2413.3. THE SUBMITTED |
| | SIZING TABLE DOES PROVIDE THE REQUIRED INFORMATION AND |
| | IS NOTED AS "FOR REFERENCE ONLY." |
| | 3) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| | SEC. G2413 |
| | 4) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| | THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A |
| | COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF |
| | PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, |
| | THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, |
| | THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. |
| | 6) THE SUBMITTED GAS RISER REFERS TO A RINNAI TANKLESS |
| | WATER HEATER BUT THE SUBMITTED SPECIFICATIONS ARE FOR A |
| | NAVIEN UNIT. CLARIFY. |
| | 7) PLEASE CORRECT THE ADDRESS ON THE GAS RISER. IT |
| | SHOULD READ 2324 EMBASSY DR. |
| | 8) IF A NAVIEN MODEL WATER HEATER IS BEING INSTALLED, |
| | IDENTIFY THE SPECIFIC MODEL THAT IS BEING INSTALLED AND |
| | THE BTU VALUE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |