| Notes |
| Date |
Text |
| 2017-07-26 08:11:41 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD AND ANCHORING PLAN IS REQUIRED TO | | | HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL | | | HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE | | | NOT ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES | | | ARE ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED | | | PLANS AND DOCUMENTS. | | | | | | 2) THE GENERATOR PAD AND ANCHORING PLAN THAT WAS | | | SUBMITTED DOES NOT LIST THE MODEL NUMBER (QT048) OF THE | | | 48 KW GENERATOR THAT YOU ARE INSTALLING. CHECK THE | | | MODELS LISTED ON THE PLANS TO BE SURE THEY MATCH THE | | | ONE YOU WILL BE INSTALLING. FBC 107.2.1 |
|