| Plan Review Notes For Permit 17070620 |
| Permit Number |
17070620 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-24 14:01:31 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070620 | | | 7/24/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ERV EXHAUST OUTLET APPEARS TO BE WITHIN THE | | | REQUIRED 10' CLEARANCE DISTANCE TO THE REAR DOOR- | | | SECTION 501.3.1(2). | | | | | | 2) SHOW THE ERV CONDENSATE PIPING RUN AND DISCHARGE | | | LOCATION. | | | | | | 3) SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA GOT | | | THE LOUVERS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|