2017-07-24 10:43:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SPECS FOR EEMAX SP2412DL RECOMMEND A WIRE SIZE OF
 #10. PROVIDE CORRECTION. NEC 110.3
 2. POWER PLAN SHOWS THE SAME CIRCUIT FOR EWH AND ERV.
 PROVIDE CORRECTION. FBC 107.2.1, NEC 408.4
 3. PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL
 SUFFICE. FBC 105.1
 4. NOTE 20 ON E-1 STATES THERE IS NO FIRE ALARM, BUT
 NOTES 5 AND 11 ON MECHANICAL DRAWING REFERENCE FIRE
 ALARM WORK. PROVIDE CORRECTION. FBC 107.2.1
 5. PROVIDE SHORT CIRCUIT CALCULATION FOR SERVICE
 FEEDERS AND RATING OF ELECTRICAL PANEL TO CONFIRM
 ADEQUATE RATING. NEC 110.9, 110.10
 6. PROVIDE AUTOMATIC CONTROL OF SHOW WINDOW OUTLETS.
 FBC C405.2.2.1, C405.2.3
 7. ELECTRICAL RISER DIAGRAM APPEARS TO SHOW A JUNCTION
 BOX BELOW SLAB. JUNCTION BOXES ARE REQUIRED TO BE
 ACCESSIBLE. PROVIDE CORRECTION. NEC 314.29
 8. SPECS FOR ERV STATE THAT THE MOCP SHOULD BE 15 AMP.
 PANEL SCHEDULE SHOWS A 20 AMP BREAKER TO THIS UNIT.
 PROVIDE CORRECTION. NEC 110.3, FBC 107.2.1
 9. CIRCUIT 32 AND 34 SHOW A #14 WIRE ON A 20 AMP
 BREAKER. PROVIDE CORRECTION. NEC 310.15(B)(16), 240.4
 10. NOTE 12 ON E-1 STATES MINIMUM WIRE SIZE SHALL BE
 #12, BUT SEVERAL CIRCUITS ARE SHOWN WITH #14 WIRE.
 CLARIFY AND/OR CORRECT. FBC 107.2.1
 11. SEVERAL OUTLETS ON CIRCUIT 10 AND 12 APPEAR TO BE
 WITHIN 6 FEET OF A SINK AND DO NOT SHOW GFCI
 PROTECTION. PROVIDE GFCI PROTECTION REQUIRED PER CODE.
 NEC 210.8
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  