| 2017-07-24 10:43:22 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. SPECS FOR EEMAX SP2412DL RECOMMEND A WIRE SIZE OF |
| | #10. PROVIDE CORRECTION. NEC 110.3 |
| | 2. POWER PLAN SHOWS THE SAME CIRCUIT FOR EWH AND ERV. |
| | PROVIDE CORRECTION. FBC 107.2.1, NEC 408.4 |
| | 3. PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT |
| | NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA, |
| | WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL |
| | SUFFICE. FBC 105.1 |
| | 4. NOTE 20 ON E-1 STATES THERE IS NO FIRE ALARM, BUT |
| | NOTES 5 AND 11 ON MECHANICAL DRAWING REFERENCE FIRE |
| | ALARM WORK. PROVIDE CORRECTION. FBC 107.2.1 |
| | 5. PROVIDE SHORT CIRCUIT CALCULATION FOR SERVICE |
| | FEEDERS AND RATING OF ELECTRICAL PANEL TO CONFIRM |
| | ADEQUATE RATING. NEC 110.9, 110.10 |
| | 6. PROVIDE AUTOMATIC CONTROL OF SHOW WINDOW OUTLETS. |
| | FBC C405.2.2.1, C405.2.3 |
| | 7. ELECTRICAL RISER DIAGRAM APPEARS TO SHOW A JUNCTION |
| | BOX BELOW SLAB. JUNCTION BOXES ARE REQUIRED TO BE |
| | ACCESSIBLE. PROVIDE CORRECTION. NEC 314.29 |
| | 8. SPECS FOR ERV STATE THAT THE MOCP SHOULD BE 15 AMP. |
| | PANEL SCHEDULE SHOWS A 20 AMP BREAKER TO THIS UNIT. |
| | PROVIDE CORRECTION. NEC 110.3, FBC 107.2.1 |
| | 9. CIRCUIT 32 AND 34 SHOW A #14 WIRE ON A 20 AMP |
| | BREAKER. PROVIDE CORRECTION. NEC 310.15(B)(16), 240.4 |
| | 10. NOTE 12 ON E-1 STATES MINIMUM WIRE SIZE SHALL BE |
| | #12, BUT SEVERAL CIRCUITS ARE SHOWN WITH #14 WIRE. |
| | CLARIFY AND/OR CORRECT. FBC 107.2.1 |
| | 11. SEVERAL OUTLETS ON CIRCUIT 10 AND 12 APPEAR TO BE |
| | WITHIN 6 FEET OF A SINK AND DO NOT SHOW GFCI |
| | PROTECTION. PROVIDE GFCI PROTECTION REQUIRED PER CODE. |
| | NEC 210.8 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |