| 2017-07-20 09:28:41 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070620 |
| | ADD: 8170 OKEECHOBEE BLVD. SUITE: 7 |
| | CONT: ATLANTIC ENGINEERING SERVICES |
| | TEL: 561-358-4140 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 20/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2 IT APPEARS THERE MAY BE A DISCREPANCY IN |
| | THE PLANS. THE 2 ELEVATION VIEWS OF THE RESTROOM THE |
| | NORTH AND EAST SHOW TILE ON THE WALLS BUT WHEN YOU GO |
| | TO THE ROOM FINISH SCHEDULE, SAME PAGE IT APPEARS THE |
| | WALLS ARE A PAINT FINISH WITH NOTE (4). PLEASE PROVIDE |
| | COMPLIANCE WITH THE 2014 FBC-B 1210.2.2 WALLS AND |
| | PARTITIONS. WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) |
| | OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE |
| | A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF |
| | NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND |
| | EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN |
| | SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY |
| | AFFECTED BY MOISTURE. |
| | |
| | 2) THE MECHANICAL SHEET M-1 NOTE #9 IS FOR THROUGH THE |
| | WALL LOUVERS FOR EITHER INTAKE OR EXHAUST AIR. |
| | SHEET M-3 DETAIL 8 IDENTIFIES THE WALL LOUVER AS A |
| | MIAMI-DADE NOA 12-0830.08. PLEASE PROVIDE FOR |
| | COMPLIANCE WITH 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31(C) WALL LOUVERS |
| | |
| | 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |