| Notes |
| Date |
Text |
| 2017-07-18 04:17:47 | THE BACKFLOW PREVENTION DEVICE SHALL BE LEAD FREE PER | | | THE CITY OF WPB CROSS CONNECTION MANUAL & 2014 | | | FBC-PLUMBING SEC.605.2.1. THE SUBMITTED SPECIFICATIONS | | | DO NOT SHOW THE DEVICE AS LEAD FREE.SUBMIT TWO COPIES | | | OF MANUFACTURER'S SPECIFICATIONS THAT SHOW THE DEVICE | | | IS LEAD FREE. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|