| Plan Review Notes For Permit 17070579 |
| Permit Number |
17070579 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-09 09:20:58 | APPROVED WITH EXCEPTION: | | | | | | PROVISO: DESIGN PROFESSIONAL SHALL PROVIDE CALCULATION | | | FOR REDUCTION IN NEUTRAL SIZE TO PANEL C PRIOR TO FINAL | | | INSPECTION. PROVIDE TO INSPECTOR AT TIME OF INSPECTION. | | | NEC 220.61 | | | |
|