| 2017-07-20 14:26:09 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. ELECTRICAL PLAN SHOWS 4 ELECTRIC COMPANY METERS, THE |
| | RISER DIAGRAM SHOWS 2. PROVIDE ACCURATE RISER DIAGRAM |
| | AND ELECTRICAL PLAN SHOWING THE LOCATION AND NAME OF |
| | EACH SERVICE AND THE CORRESPONDING SERVICE EQUIPMENT, |
| | AND THE RATING OF EACH DISCONNECT AND PANEL. NEC 215.5, |
| | 408.30, FBC 107.2.1 |
| | 2. RISER DIAGRAM FOR PANEL C SHOWS 3-3/0 CONDUCTORS IN |
| | A 2 INCH CONDUIT FEEDING THE INTERIOR PANEL. AN |
| | EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED IN THIS |
| | CONDUIT. PROVIDE CORRECTION. NEC 250.122, 250.24(A)(5) |
| | 3. RISER DIAGRAM FOR PANEL A SHOWS 3/0 CONDUCTORS, |
| | WHICH IS RATED FOR 200 AMPS. THE LOAD CALCULATION |
| | PROVIDED FOR PANEL A AND PANEL B ADDED TOGETHER EQUALS |
| | 206 AMPS, WHICH EXCEEDS THE RATING OF THE WIRE. THE |
| | LOAD FOR PANEL B IS NOT INCLUDED IN THE PANEL SCHEDULE |
| | FOR PANEL A, BUT IS SHOWN ON THE RISER AS BEING FED |
| | FROM PANEL A. PROVIDE ACCURATE LOAD CALCULATION AND |
| | CIRCUIT DIRECTORY FOR PANEL A, PROVIDE PROPERLY SIZED |
| | FEEDERS. NEC 215.2, 215.5, 220, 408.4, 310.15(B)(16) |
| | 4. IN ADDITION TO COMMENT #3, PANEL B IS SHOWN AS A |
| | MAIN LUG ONLY PANEL. IF THIS IS ACCURATE, PROVIDE OVER |
| | CURRENT PROTECTION DETAILS. NEC 215.2, 240.4, 408.30, |
| | FBC 107.2.1 |
| | 5. IF PANEL B IS FED FROM PANEL A, WHICH IS SHOWN AS A |
| | 200 AMP PANEL, THEN THIS PANEL IS ALSO OVERLOADED. |
| | PROVIDE CORRECTION. NEC 408.30 |
| | 6. THE WIRE FEEDING PANEL B DOES NOT INCLUDE THE |
| | REQUIRED EQUIPMENT GROUNDING CONDUCTOR. PROVIDE |
| | CORRECTION. NEC 250.122, 250.24(A)(5) |
| | 7. EMERGENCY AND EXIT LIGHTS MUST BE ON THE SAME |
| | CIRCUIT AS THE LIGHTS IN THE SAME AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 8. PROVIDE REQUIRED SIGN CIRCUIT, WITH CONTROLS PER THE |
| | FBC ENERGY CODE. NEC 600.5, FBC C405.2.4 |
| | 9. PROVIDE SHOW WINDOW OUTLETS IF APPLICABLE. NEC |
| | 210.62 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |