2017-07-20 14:26:09CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL PLAN SHOWS 4 ELECTRIC COMPANY METERS, THE
 RISER DIAGRAM SHOWS 2. PROVIDE ACCURATE RISER DIAGRAM
 AND ELECTRICAL PLAN SHOWING THE LOCATION AND NAME OF
 EACH SERVICE AND THE CORRESPONDING SERVICE EQUIPMENT,
 AND THE RATING OF EACH DISCONNECT AND PANEL. NEC 215.5,
 408.30, FBC 107.2.1
 2. RISER DIAGRAM FOR PANEL C SHOWS 3-3/0 CONDUCTORS IN
 A 2 INCH CONDUIT FEEDING THE INTERIOR PANEL. AN
 EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED IN THIS
 CONDUIT. PROVIDE CORRECTION. NEC 250.122, 250.24(A)(5)
 3. RISER DIAGRAM FOR PANEL A SHOWS 3/0 CONDUCTORS,
 WHICH IS RATED FOR 200 AMPS. THE LOAD CALCULATION
 PROVIDED FOR PANEL A AND PANEL B ADDED TOGETHER EQUALS
 206 AMPS, WHICH EXCEEDS THE RATING OF THE WIRE. THE
 LOAD FOR PANEL B IS NOT INCLUDED IN THE PANEL SCHEDULE
 FOR PANEL A, BUT IS SHOWN ON THE RISER AS BEING FED
 FROM PANEL A. PROVIDE ACCURATE LOAD CALCULATION AND
 CIRCUIT DIRECTORY FOR PANEL A, PROVIDE PROPERLY SIZED
 FEEDERS. NEC 215.2, 215.5, 220, 408.4, 310.15(B)(16)
 4. IN ADDITION TO COMMENT #3, PANEL B IS SHOWN AS A
 MAIN LUG ONLY PANEL. IF THIS IS ACCURATE, PROVIDE OVER
 CURRENT PROTECTION DETAILS. NEC 215.2, 240.4, 408.30,
 FBC 107.2.1
 5. IF PANEL B IS FED FROM PANEL A, WHICH IS SHOWN AS A
 200 AMP PANEL, THEN THIS PANEL IS ALSO OVERLOADED.
 PROVIDE CORRECTION. NEC 408.30
 6. THE WIRE FEEDING PANEL B DOES NOT INCLUDE THE
 REQUIRED EQUIPMENT GROUNDING CONDUCTOR. PROVIDE
 CORRECTION. NEC 250.122, 250.24(A)(5)
 7. EMERGENCY AND EXIT LIGHTS MUST BE ON THE SAME
 CIRCUIT AS THE LIGHTS IN THE SAME AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 8. PROVIDE REQUIRED SIGN CIRCUIT, WITH CONTROLS PER THE
 FBC ENERGY CODE. NEC 600.5, FBC C405.2.4
 9. PROVIDE SHOW WINDOW OUTLETS IF APPLICABLE. NEC
 210.62
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  