2017-07-26 15:13:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070566
 7/26/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE FIRE
 SUPPRESSION SYSTEM, AND THE KITCHEN BUILD-OUT INCLUDING
 THE COOKING APPLIANCES AND GAS WORK- SECTION 107.2.1
 WPB AMENDMENTS TO THE FBC.
  
 2) A SMOOTH, CLEANABLE, NON-ABSORBENT AND
 NON-COMBUSTIBLE MATERIAL SHALL BE INSTALLED BETWEEN THE
 HOOD AND THE WALL EXTENDING NOT LESS THAN 18" IN ALL
 DIRECTIONS FROM THE HOOD- SECTION 507.9 EXCEPTION.
  
 3) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF THE MUA
 INTAKE AND THE EXHAUST FAN AND ALL REQUIRED CLEARANCE
 DISTANCE MEASUREMENTS FROM MECHANICAL AND GRAVITY
 EXHAUST OUTLETS AND AIR INTAKES, AND ROOF EDGES-
 SECTIONS 304.11, 401.4, 506.3.13.3
  
 4) PROVIDE WIND LOAD ENGINEERING AND WIND LOAD DESIGN
 CRITERIA FOR INSTALLATION OF THE MUA CURB AND THE
 EXHAUST FAN AND CURB- SECTION 301.15.
  
 5) SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE DUCT
 WRAP- SECTION 506.3.11.2.
  