| Plan Review Notes For Permit 17070538 |
| Permit Number |
17070538 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-09-29 19:03:49 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENERGY FORMS CONTAIN ERRORS AND DO NOT | | | ACCURATELY REFLECT THE DATA THAT IS SHOWN ON THE PLANS. | | | FBC 107.2.1 | | | - THERE IS ONLY ONE BEDROOM AND IT IS LOCATED ON THE | | | SECOND FLOOR. THE FORM HAS THREE (3) BEDROOMS. ONE ONE | | | THE FIRST FLOOR AND TWO ON THE SECOND FLOOR. THE FIRST | | | FLOOR IS A GARAGE AND STORAGE AND THE SECOND FLOOR HAS | | | ONLY ONE (1) BEDROOM. | | | - THE PLANS DO NOT SHOW A WHOLE HOUSE FAN. HOWEVER, THE | | | CREDIT FOR ONE IS LISTED ON THE FORMS. THE PLANS STATE | | | THAT THIS STRUCTURE HAS AN UNVENTED ATTIC, SUBMIT | | | DOCUMENTS THAT SHOW HOW THE REQUIREMENTS OF FBC ENERGY | | | CONSERVATION R405.7.5 WILL BE MET. | | | - THE WINDOW OPENINGS AND ORIENTATIONS LISTED ON THE | | | FORMS DO MATCH THE ONES THAT ARE SHOWN ON THE PLANS. | | | TWELVE (12) WINDOW OPENINGS ARE LISTED ON THE FORMS AND | | | SIXTEEN (16) ARE SHOWN ON THE PLANS. PLEASE CORRECT FBC | | | 107.2.1 AND FBC ENERGY CONSERVATION R 101.5.1.1.1 | | | - THE OWNER / AGENT IS REQUIRED TO SIGN AND DATE THE | | | ENERGY FORM 402. FBC ENERGY CONSERVATION R103.1.1.2 | | | |
|