| Plan Review Notes For Permit 17070538 |
| Permit Number |
17070538 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-29 18:46:24 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENERGY FORMS CONTAIN ERRORS AND DO NOT | | | ACCURATELY REFLECT THE DATA THAT IS SHOWN ON THE PLANS. | | | FBC 107.2.1 | | | - THERE IS ONLY ONE BEDROOM AND IT IS LOCATED ON THE | | | SECONG FLOOR. | | | - THE PLANS DO NOT SHOW THAT THERE IS AN UNVENTED | | | ATTIC. | | | - THE R-VALUE OF THE ATTIC INSULATION IS LISTED AS 0 | | | FOR THE BLOWN INSULATION. | | | - THE MINIMUM R-VALUE FOR DUCTS IS R-6 PER FBC ENERGY | | | CONSERVATION R405.2 | | | -THE COMBINED KBTU OF THE HEATING SYSTEMS IS 36.0 PER | | | THE MECHANICAL PLANS. | | | - THE PLANS DO NOT SHOW CEILING FANS OR A WHOLE HOUSE | | | FAN. HOWEVER, THESE CREDITS ARE LISTED ON THE FORMS. | | | - THE FLOOR/CEILING ASSEMBLY AND THE INTERIOR WALLS | | | THAT SEPARATE THE GARAGE AND STORAGE FROM THE DWELLING | | | UNIT SHOULD BE THERMALLY INSULATED. | | | |
|