| 2017-08-03 10:59:02 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ACCORDING TO THE FBC EXISTING BUILDING SECTION 505, |
| | THIS IS A LEVEL 3 ALTERATION. |
| | |
| | 2) BASED ON THE PLANS THAT WERE SUBMITTED, THIS |
| | STRUCTURE HAS A MEAN ROOF HEIGHT OF 23 FEET AND IS |
| | LOCATED IN EXPOSURE CATEGORY "D" WITH A 175 MPH VULT |
| | WIND SPEED. PLEASE PROVIDE THE WINDSPEED DESIGN DATA ON |
| | THE PLANS. FBC-R301.2.1 |
| | |
| | 3) THE REQUIRED DESIGN PRESSURES FOR THE WINDOWS AND |
| | DOORS THAT ARE SPECIFIED ON THE PLANS APPEAR TO BE |
| | BASED ON EXPOSURE CATEGORY "C". PLEASE REVIEW AND |
| | ADJUST AS NECESSARY. FBC-R301.1 |
| | |
| | 4) THE REQUIRED DESIGN PRESSURES FOR THE NEW SECTIONAL |
| | GARAGE DOORS WERE NOT SPECIFIED ON THE PLANS. PLEASE |
| | SPECIFY THEM ON THE PLANS. FBC 107.2.1 |
| | |
| | 5) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 6) ON SHEET A104 THE WEST AND NORTH ELEVATIONS ARE BOTH |
| | INCORRECTLY IDENTIFIED AS EAST ELEVATIONS. PLEASE |
| | CORRECT. FBC 107.2.1 |
| | |
| | 7) PLEASE IDENTIFY THE REQUIRED EGRESS WINDOW FOR THE |
| | SECOND FLOOR BEDROOM ON THE PLANS. FBC-R310.1 EMERGENCY |
| | ESCAPE AND RESCUE REQUIRED. FBC-R310.1.1 MINIMUM |
| | OPENING AREA. ALL EMERGENCY ESCAPE AND RESCUE OPENINGS |
| | SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 SQUARE |
| | FEET |
| | |
| | |
| | |
| | |
| | |
| | |