2017-08-21 06:18:421) CITY RECORDS SHOW A PREVIOUS GAS PERMIT AT THIS
 ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST
 BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3. 2ND REQUEST.
 2) THE PERMIT APPLICATION IS FOR ONE GENERATOR BUT THE
 SUBMITTTED PLAN SHOWS 2 GENERATORS.PERMIT #17080576
 SHOWS ONLY ONE GENERATOR TO BE INSTALLED BUT THE
 SUBMITTED GAS PLAN SHOWS TWO GENERATORS. CLARIFY. THE
 DESCRIPTION OF WORK ON THE APPLICATION SHALL CORRELATE
 WITH THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 3) THE GAS PLAN APPEARS TO SHOW GALVANIZED PIPING
 UNDERGROUND WHICH IS NOT PERMITTED BY THE 2014 FUEL GAS
 CODE SEC.404.11, 404.11.1. 2ND REQUEST.
 4) SHOW THE BTU LOAD FOR EACH GENERATOR. 2014 FBC-FUEL
 GAS SECS. 401.8 THROUGH 402.2. 2ND REQUEST.
 5) THE SIZING TABLE THAT WAS SUBMITTED IS FROM THE 2009
 INTERNATIONAL FUEL GAS CODE. THE CODE IN EFFECT IS THE
 2014 FBC-FUEL GAS CODE. 2ND REQUEST.
 6) SUBMIT TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE GENERATORS AND THE LOCATION OF THE GAS METERS.
 WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
 7) CLARIFY HOW THE GALVANIZED PIPE TO THE 48 KW & 45 KW
 GENERATOR WILL BE INSTALLED. THE PLAN REFERS TO THE
 PIPE BEING MOUNTED ON A WALL BUT THE PLANS DO NOT SHOW
 ANY WALL FOR THIS PIPE TO BE MOUNTED.CLARIFY. SUBMIT
 TWO COPIES OF A SURVEY SHOWING THE LOCATION OF THE
 WALLS.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1. THE SPECIFICATION
 THAT HAS BEEN SUBMITTED HAS NO INFORMATION AS TO THE
 MANUFACTURER EXCEPT WHAT IS WRITTEN ON IT. SUBMIT
 DOCUMENTATION THAT SHOWS THE MANUFACTURER OF THE
 REGULATOR THAT IS BEING INSTALLED. 2ND REQUEST.
  
 I SUGGEST CONTACTING THIS REVIEWER TO DISCUSS THESE
 PLAN REVIEW COMMENTS.
  