| Date |
Text |
| 2017-08-21 06:18:42 | 1) CITY RECORDS SHOW A PREVIOUS GAS PERMIT AT THIS |
| | ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST |
| | BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO |
| | ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF |
| | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. 2ND REQUEST. |
| | 2) THE PERMIT APPLICATION IS FOR ONE GENERATOR BUT THE |
| | SUBMITTTED PLAN SHOWS 2 GENERATORS.PERMIT #17080576 |
| | SHOWS ONLY ONE GENERATOR TO BE INSTALLED BUT THE |
| | SUBMITTED GAS PLAN SHOWS TWO GENERATORS. CLARIFY. THE |
| | DESCRIPTION OF WORK ON THE APPLICATION SHALL CORRELATE |
| | WITH THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1. 2ND |
| | REQUEST. |
| | 3) THE GAS PLAN APPEARS TO SHOW GALVANIZED PIPING |
| | UNDERGROUND WHICH IS NOT PERMITTED BY THE 2014 FUEL GAS |
| | CODE SEC.404.11, 404.11.1. 2ND REQUEST. |
| | 4) SHOW THE BTU LOAD FOR EACH GENERATOR. 2014 FBC-FUEL |
| | GAS SECS. 401.8 THROUGH 402.2. 2ND REQUEST. |
| | 5) THE SIZING TABLE THAT WAS SUBMITTED IS FROM THE 2009 |
| | INTERNATIONAL FUEL GAS CODE. THE CODE IN EFFECT IS THE |
| | 2014 FBC-FUEL GAS CODE. 2ND REQUEST. |
| | 6) SUBMIT TWO COPIES OF A SURVEY SHOWING THE LOCATION |
| | OF THE GENERATORS AND THE LOCATION OF THE GAS METERS. |
| | WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST. |
| | 7) CLARIFY HOW THE GALVANIZED PIPE TO THE 48 KW & 45 KW |
| | GENERATOR WILL BE INSTALLED. THE PLAN REFERS TO THE |
| | PIPE BEING MOUNTED ON A WALL BUT THE PLANS DO NOT SHOW |
| | ANY WALL FOR THIS PIPE TO BE MOUNTED.CLARIFY. SUBMIT |
| | TWO COPIES OF A SURVEY SHOWING THE LOCATION OF THE |
| | WALLS. |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1. THE SPECIFICATION |
| | THAT HAS BEEN SUBMITTED HAS NO INFORMATION AS TO THE |
| | MANUFACTURER EXCEPT WHAT IS WRITTEN ON IT. SUBMIT |
| | DOCUMENTATION THAT SHOWS THE MANUFACTURER OF THE |
| | REGULATOR THAT IS BEING INSTALLED. 2ND REQUEST. |
| | |
| | I SUGGEST CONTACTING THIS REVIEWER TO DISCUSS THESE |
| | PLAN REVIEW COMMENTS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |