| Plan Review Notes For Permit 17070522 |
| Permit Number |
17070522 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-17 10:56:09 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- ACCORDING TO THE APPROVED APPLICATIONS ON PAGE 4 OF | | | 7 OF THE COBRA RIDGE VENT NOA 16-0217.02 SUBMITTED, THE | | | MINIMUM SLOPE IS 3:12. PERMIT APPLICATION SPECIFIES A | | | ROOF SLOPE OF 2:12. THEREFORE, THE RIDGE VENT CAN NOT | | | BE INSTALLED. PROVIDE ANOTHER PRODUCT APPROVAL THAT | | | ALLOWS RIDGE VENT INSTALLATION IN THE 2:12 SLOPE OR | | | ADVICE IF ROOF VENT IS NOT GOING TO BE INSTALLED. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|