| Plan Review Notes For Permit 17070502 |
| Permit Number |
17070502 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-04 10:50:26 | SUBMITTAL DOES NOT INDICATE THE LOCATION OF THE DOORS | | | TO BE TREATED WITH INTUMESCENT PAINT. | | | | | | SUBMIT PRODUCT DATA AND THIRD PARTY LISTING FOR THE | | | PRODUCT TO BE USED. | | | | | | THE LISTING FOR A FIRE RATED DOOR IS AN ENTIRE LISTED | | | ASSEMBLY INCLUDING THE DOOR, HARDWARE, AND FRAME ETC. | | | HOW WILL THE ENTIRE DOOR ASSEMBLY MAINTAIN ITS RATING | | | UTILIZING INTUMESCENT PAINT? | | | | | | WESLEY JOLIN | | | ASSISTAN FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|