Plan Review Notes
Plan Review Notes For Permit 17070490
Permit Number 17070490
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-25 09:12:47CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE PANEL SCHEDULE FOR PANEL K, INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE. NEC
 215.5, 408.4, 600.5; FBC 107.2.1
 2. PROVIDE BLOCK NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR SIGN. FBC 105.1
 3. INDICATE WIE SIZE ON PLAN, INCLUDE ANY NECESSARY
 ACCOMODATIONS FOR VOLTAGE DROP. FBC C405.7.3.2, FBC
 107.2.1
 4. PLAN INDICATES A TIME SWITCH WITH PHOTOCELL FOR
 CONTROL OF THE SIGN, BUT ALSO SHOWS 3 SWITCHES. WHAT IS
 THE PURPOSE OF THE SWITCHES? CLARIFY AND/OR CORRECT.
 FBC 107.2.1, FBC C405.2.4
 5. LOCATION OF ELECTRICAL COMPONENTS IS DIFFICULT TO
 SEE ON PLAN DUE TO THE BACKGROUND BEING FADED
 SUBSTANTIALLY. PROVIDE CLEAR PLAN FOR REVIEW. FBC
 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  