| 2017-07-27 14:37:22 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070490 |
| | ADD: 1111 S. FLAGLER DR. |
| | CONT: MYRICK GUROSKY & ASSOC. |
| | TEL: 205-313-3027 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 27/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A101 INDICATES WINDOW AND DOOR TYPES ON THIS |
| | SHEET AS WELL AS DOOR SCHEDULE AND NOTES. NOTE # 1 |
| | INDICATES THE EXTERIOR STOREFRONT OPENING IS TO BE |
| | LARGE MISSILE RATED, AND MUST MEET THE WIND LOAD |
| | REQUIREMENTS FOR THE LOCAL WIND SPEED. THE DESIGNER OF |
| | RECORD HAS NOT SPECIFIED THE WIND DESIGN CRITERIA. |
| | UNKNOWNS TO BASE THE WIND DESIGN, DOES THIS BUILDING |
| | WHOSE PRIMARY OCCUPANCY IS PUBLIC ASSEMBLY WITH AN |
| | OCCUPANT LOAD GREATER THAN 300. IF SO, THEN THE |
| | BUILDINGS RISK CATEGORY IS INCREASED TO III SEE THE |
| | 2014 FBC-B TABLE 1604.5. WITH THE BUILDINGS RISK |
| | CATEGORY BEING III FIGURE 1609B PUTS THE WIND SPEED AT |
| | 180 VULT. |
| | |
| | 2) 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 2.2. RISK CATEGORY. |
| | |
| | 2.3HEIGHT AND EXPOSURE. WIND EXPOSURE. APPLICABLE WIND |
| | DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. |
| | TABLE 1609.7.2. |
| | |
| | 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | PLEASE CONVERT ALL WIND PRESSURES INTO VASD SINCE THE |
| | PRODUCT APPROVALS ARE IN VASD. |
| | |
| | 3) SHEET A101 INDICATES NEW STOREFRONT WINDOWS AND |
| | DOORS. PLEASE SUBMIT PRODUCT APPROVAL FOR REVIEW. 2014 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS |
| | |
| | 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) SHEET A101 IN THE DOOR SCHEDULE NOTE# 4 NOTE A |
| | INDICATES CYLINDER LOCK AND NOTE B POWER OR MANUAL |
| | PANIC HARDWARE. PLEASE REFER BACK TO FBC-B 1008.1.9.3 |
| | (2) ONLY ALLOWS THE USE OF KEY OPERATED LOCKING DEVISES |
| | WHEN THE OCCUPANT LOAD IS LESS THAN 300. PLEASE VERIFY |
| | THE OCCUPANT LOAD OF THE BUILDING. |
| | |
| | 7) SHEET A501: |
| | 7A) DETAIL # 1 OF THE INDICATES A BRICK SUPPORT, UNDER |
| | PERMIT 17010099 THE PLANS INDICATE, PROVIDE AND INSTALL |
| | NEW GAL/ PAINTED BRICK LINTEL TO EXTEND 8 INCHES PAST |
| | THE OPENING. NEITHER PLAN TRULY IDENTIFIES THE SIZE OF |
| | THE BRICK ANGLE LINTEL? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 7B) NEITHER THIS SHEET NOR A101 INDICATE IF THE DOORS |
| | ARE GOING TO HAVE MANUAL DOORS OR POWER OPERATED, |
| | ASSIST DOORS. THE NOTE # 2 ON SHEET A101 HAS OR, THE |
| | PLANS NEED TO BE SPECIFIC. 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.3: W.P.B. ADMINISTRATIVE CODE, |
| | SUCH INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL |
| | CODES "SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR |
| | THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A |
| | SUBSTITUTE FOR SPECIFIC INFORMATION". |
| | |
| | 7C) DETAIL 2 INDICATES THE EXISTING FOUNDATION NEW |
| | BLOCK WORK BENEATH GRADE AND TO FILL THE SPACE BETWEEN |
| | THE EXISTING FOUNDATION AND BLOCKWORK WITH GROUT. THE |
| | PLANS DO NOT MENTION THE REQUIREMENT FOR TERMITE |
| | TREATMENT SEE SECTION 1403.8 EXCEPTION # 4. . IF THE |
| | PATIO HAS BEEN SOIL TREATED FOR TERMITES, THE FINISH |
| | ELEVATION MAY MATCH THE BUILDING INTERIOR FINISH FLOOR |
| | ELEVATIONS ON MASONRY CONSTRUCTION ONLY. |
| | |
| | 7D) DETAIL # 2 THE SUN SCREEN DOES NOT PROVIDE THE WIND |
| | DESIGN PARAMETERS FOR THE SUN SHADE TO BE MANUFACTURED |
| | AND INSTALLED. 105.5.1 LOADS. |
| | RIGID AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO |
| | RESIST THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE |
| | (FBC-B). |
| | |
| | 7E) DETAIL # 2 INDICATES THE USE OF 4 INCH STONE VENEER |
| | BUT THE PLANS DO NOT STATE HOW THE STONE VENEER IS TO |
| | BE ANCHORED, FBC-B 1405.7. |
| | |
| | 7F) DETAIL # 2 THE WINDOW DETAIL INDICATES THE |
| | INSTALLATION OF A NEW GALVANIZED STEEL LINTEL ANGLE, |
| | THE PLANS DO NOT PROVIDE THE SIZE OF THE ANGLE NOR HOW |
| | FAR BEYOND THE WINDOW THE ANGLE NEEDS TO EXTEND? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7G) THE NOTES INDICATE THE ANCHORING OF THE SUNSHADE |
| | WITH A ? INCH STEEL PLATE AND (2) ? INCH GALVANIZED |
| | DEFORMED STEEL PINS INTO THE EXISTING CONCRETE BEAM AND |
| | EPOXY. THE PLANS DO NOT PROVIDE HOW DEEP OF A HOLE IS |
| | TO BE CREATED, HOW LONG THE STEEL PINS NEED TO BE |
| | EMBEDDED, THE TYPE OF WELD TO ATTACH THE GALVANIZED |
| | PINS TO THE STEEL PLATE. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 7H) OVER THE EXTERIOR DOORS THE PLANS SHOW A NEW |
| | PREFABBED CANOPY OVER ALUMINUM PURLINS. THERE IS NO |
| | WIND DESIGN CRITERIA, THIS DETAIL SEEMS TO BE MORE OF A |
| | CONCEPTUAL DESIGN NO INFORMATION WAS PROVIDED. |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. 2010 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |