| Plan Review Notes For Permit 17070457 |
| Permit Number |
17070457 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-12-01 14:24:34 | APPROVED WITH PROVISO: | | | | | | 1- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING ON | | | PLANS. IF SPECIFYING SCREWS, THEN SPECIFY SIZE AND | | | NUMBER TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES | | | OF SEC. R301.1 FBC-RESIDENTIAL. IF SPECIFYING ROOF TILE | | | ADHESIVE, THEN PRODUCT APPROVAL IS REQUIRED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) FLAT ROOF AS SHOWN ON PLANS ABOVE SECOND FLOOR ROOF. | | | NOTE: CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE | | | INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE | | | DESIGN PRESSURES FOR ALL ROOF ZONES. | | | | | | B) BALCONIES UNDERLAYMENT DESIGNED TO RECEIVE | | | TILE/STONE AS SPECIFIED ON PLANS. NOTE: CLEARLY | | | IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED AND | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF | | | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR | | | ALL ROOF ZONES. | | | | | | | | | | | | APPROVED PRODUCT APPROVALS: | | | 1) ROOF TILE NOA 12-0904.12. | | | 2)ROOF TILE ADHESIVE FL6332-R7 FOR AH160. |
|