| 2017-11-28 14:03:56 | 1- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| | SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301.1 FBC-RESIDENTIAL. IF SPECIFYING ROOF TILE |
| | ADHESIVE, THEN PRODUCT APPROVAL IS REQUIRED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES. |
| | RESPONSE: |
| | DESIGNER OF RECORD TO PROVIDE PROPOSED ROOF TILE |
| | FASTENING SPECIFICATIONS ON PLANS. DON'T PROVIDE |
| | GENERAL SPECIFICATIONS LIKE PER "PRODUCT APPROVAL". |
| | PRODUCT APPROVAL IS JUST TO VERIFY THAT THE PRODUCT |
| | APPROVAL MEETS THE DESIGN CRITERIA SPECIFIED BY THE |
| | DESIGNER OF RECORD. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) FLAT ROOF AS SHOWN ON PLANS ABOVE SECOND FLOOR ROOF. |
| | NOTE: CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE |
| | DESIGN PRESSURES FOR ALL ROOF ZONES. |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | B) BALCONIES UNDERLAYMENT DESIGNED TO RECEIVE |
| | TILE/STONE AS SPECIFIED ON PLANS. NOTE: CLEARLY |
| | IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED AND |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ALL ROOF ZONES. |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | |
| | |
| | APPROVED PRODUCT APPROVALS: |
| | 1) ROOF TILE NOA 12-0904.12. |
| | 2)ROOF TILE ADHESIVE FL6332-R7 FOR AH160. |