Plan Review Notes
Plan Review Notes For Permit 17070457
Permit Number 17070457
Review Stop B
Sequence Number 2
Notes
Date Text
2017-11-27 16:06:26NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR WILL BRING REQUIRED INFORMATION
 PRIOR TO INSPECTIONS TO AVOID CONFLICTS/DELAYS.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF
 PROVISO OPTION PREFERRED AT THIS TIME OR IF
 RE-SUBMITTING REQUIRED INFORMATION. IMPACT FEES MUST BE
 PAID BEFORE PROCESSING THE PERMIT.
  
 1- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS,
 INCLUDING ALL FRAMING MEMBERS AND CONNECTORS FOR THE
 CONSTRUCTION OF:
 A) METAL LOUVERS SHOWN ON THE EXTERIOR ELEVATIONS.
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER SAYS SEE NEW SHEET A6.2.
 THERE IS NOT SHEET A6.2 SUBMITTED. PROVIDE COMPLETE
 INFORMATION.
  
 B) METAL BAHAMA SHUTTERS SHOWN ON THE EXTERIOR
 ELEVATIONS.
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER SAYS SEE NEW SHEET A6.2.
 THERE IS NOT SHEET A6.2 SUBMITTED. PROVIDE COMPLETE
 INFORMATION.
  
 C) METAL COLONIAL SHUTTERS SHOWN ON THE EXTERIOR
 ELEVATIONS.
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER SAYS SEE NEW SHEET A6.2.
 THERE IS NOT SHEET A6.2 SUBMITTED. PROVIDE COMPLETE
 INFORMATION.
  
 D) ALUMINUM TRELLIS SHOWN ON THE EXTERIOR ELEVATIONS
 AND PLANS.
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER SAYS SEE NEW SHEET A6.2.
 THERE IS NOT SHEET A6.2 SUBMITTED. AND DETAIL 5/A-4 IS
 MISSING INFORMATION. PROVIDE COMPLETE INFORMATION.
  
 2- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. IF SPECIFYING ROOF TILE
 ADHESIVE, THEN PRODUCT APPROVAL IS REQUIRED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES.
 RESPONSE:
 DESIGNER OF RECORD TO PROVIDE PROPOSED ROOF TILE
 FASTENING SPECIFICATIONS ON PLANS. DON'T PROVIDE
 GENERAL SPECIFICATIONS LIKE PER "PRODUCT APPROVAL".
 PRODUCT APPROVAL IS JUST TO VERIFY THAT THE PRODUCT
 APPROVAL MEETS THE DESIGN CRITERIA SPECIFIED BY THE
 DESIGNER OF RECORD.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF AS SHOWN ON PLANS ABOVE SECOND FLOOR ROOF.
 NOTE: CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES.
 RESPONSE: NOT ADDRESSED.
  
 B) BALCONIES UNDERLAYMENT DESIGNED TO RECEIVE
 TILE/STONE AS SPECIFIED ON PLANS. NOTE: CLEARLY
 IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES.
 RESPONSE: NOT ADDRESSED.
  
 C) FRENCH DOORS NOA 15-0602.09 SUBMITTED: DRAWINGS
 SUBMITTED WITH THIS NOA ARE NOT LEGIBLE. THEY ARE CUT
 IN PIECES. PROVIDE COMPLETE AND LEGIBLE DRAWINGS.
 RESPONSE: NOT ADDRESSED.
  
 D) FIXED WINDOWS AS SHOWN ON PLANS.
 RESPONSE: (1) CLEARLY IDENTIFY GLASS TYPE AND ANCHOR
 TYPE ON THE DESIGN LOAD TABLE ON DRAWING SHEET 3 OF 7
 OF NOA 14-0923.08 TO VERIFY COMPLIANCE WIT THE
 CALCULATED DESIGN PRESSURES.
 NOTE: SOME WINDOWS SHOWN ON SHEET 3 OF 7 DON'T MEET THE
 CALCULATED DESIGN PRESSURES.
 (2) PROVIDE PRODUCT APPROVAL FOR SIDELITE WINDOW "P"
 SPECIFIED FOR DINING ROOM FRENCH DOORS. OR PROVIDE
 PRODUCT APPROVAL FOR FRENCH DOORS WITH SIDELITES AS
 SHOWN ON PLANS.
  
 E) WINDOW AND DOOR MULLIONS AS SHOWN ON PLANS. AND
 SPECIFY MULLION SIZE FOR EACH APPLICATION TO VERIFY
 COMPLIANCE WITH THE DESIGN-PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: FOR THE FRENCH DOORS YOU MAY
 SUBMIT THE PRODUCT APPROVAL FOR FRENCH DOORS WITH
 SIDELITES.
 RESPONSE: NOT ADDRESSED.
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, WALL SECTIONS AND DETAILS. NOTE: PROVIDE ONLY
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR LIST THE FLORIDA
 PRODUCT APPROVAL NEXT TO EACH CONNECTOR.
 RESPONSE: NEED TO PROVIDE CURRENT EVALUATION REPORTS OR
 CURRENT FLORIDA PRODUCT APPROVAL REPORTS. REPORTS
 SUBMITTED ARE EXPIRED.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 ******NOTE:
 PROVIDE MANUFACTURER'S SPECS FOR THE CASEMENT EGRESS
 WINDOWS SHOWING THAT THE SPECIFIED SIZES MEET ALL THE
 EGRESS REQUIREMENTS, INCLUDING THE WINDOWS ON THE
 SECOND FLOOR. ******PROVIDE INFORMATION PRIOR TO
 PURCHASING WINDOWS TO AVOID CONFLICTS.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS.
  