| Notes |
| Date |
Text |
| 2017-08-04 19:27:41 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) FLAT ROOF AS SHOWN ON PLANS ABOVE SECOND FLOOR ROOF. | | | NOTE: CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE | | | INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE | | | DESIGN PRESSURES FOR ALL ROOF ZONES. | | | | | | B) BALCONIES UNDERLAYMENT DESIGNED TO RECEIVE | | | TILE/STONE AS SPECIFIED ON PLANS. NOTE: CLEARLY | | | IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED AND | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF | | | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR | | | ALL ROOF ZONES. | | | | | | C) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF | | | RECORD. SEE ROOF TILE NOA FOR LISTED ADHESIVES. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
|