| Plan Review Notes For Permit 17070457 |
| Permit Number |
17070457 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-26 16:58:07 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. ON THE RISER DIAGRAM THE SHOWER IN THE MASTER BATH | | | SHALL CONNECT TO THE WET VENT SEPARATELY FROM THE TUB. | | | PER FBC RES P3108.1 | | | | | | 2. ON THE RISER DIAGRAM BATHROOM #4 THE WC IS NOT | | | VENTED PROPERLY IT SHOULD CONNECT TOGETHER WITH THE SHR | | | AND LAV AS A WET VENTED BATHROOM GROUP. PER PER FBC RES | | | P3108.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|