| 2017-07-28 09:08:15 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LOAD CALCULATION SHOWS A "PANEL C". HOWEVER, THIS IS |
| | NOT SHOWN ON RISER DIAGRAM OR PLAN, AND THERE IS NO |
| | PANEL SCHEDULE FOR IT. PLEASE CLARIFY AND/OR CORRECT. |
| | FBC 107.2.1 |
| | 2. PANEL A, CIRCUITS 33,35 AND 34,36 SHOW #6 ROMEX ON A |
| | 60 AMP BREAKER. #6 ROMEX WIRE IS NOT RATED FOR 60 AMPS. |
| | THERE IS NO MECHANICAL PLAN TO CONFIRM THE REQUIREMENTS |
| | OF THE UNITS. PROVIDE CORRECTION. NEC 334.80; FBC |
| | RE3705.4.4; FBC 107.2.1, 107.3.5 |
| | 3. PANEL B, CIRCUIT 37,39 SHOW #6 ROMEX ON A 60 AMP |
| | BREAKER. #6 ROMEX WIRE IS NOT RATED FOR 60 AMPS. THERE |
| | IS NO MECHANICAL PLAN TO CONFIRM THE REQUIREMENTS OF |
| | THE UNITS. PROVIDE CORRECTION. NEC 334.80; FBC |
| | RE3705.4.4; FBC 107.2.1, 107.3.5 |
| | 4. PROVIDE BLOCK NOTE THAT SEPARATE PERMITS WILL BE |
| | REQUIRED FOR POOL AND LOW VOLTAGE SYSTEMS. FBC 105.1 |
| | 5. PANEL P, CIRCUITS 1,3 AND 5,7 AND 6,8 AND POSSIBLY |
| | 10 REQUIRE GFCI PROTECTION. WILL THESE BREAKERS BE |
| | INSTALLED UNDER THIS PERMIT IN PREPARATION FOR THE POOL |
| | UNDER SEPARATE PERMIT? IF NOT, PROVIDE NOTE THAT FUTURE |
| | INSTALLATION TO COMPLY. NEC 680.21(C), 680.44; FBC |
| | RE4203.1.3, RE4208.1; FBC 107.2.1 |
| | 6. NOTE # 19 STATES THAT CLOSET LIGHTING SHALL COMPLY |
| | WITH NEC 410.8, WHICH IS NOT THE CORRECT CODE SECTION |
| | FOR CLOSET LIGHTING. PROVIDE CORRECTION. NEC 410.16; |
| | FBC RE4003.12 |
| | 7. NOTE # 24 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE4002.14 |
| | 8. BLOCK NOTE ON SHEET A-3.1 STATES THAT IF THERE ARE |
| | MORE THAN 6 SMOKE DETECTORS, A LOW VOLTAGE SYSTEM |
| | SHOULD BE INSTALLED. THIS HOUSE HAS MORE THAN 6. IF THE |
| | INTENTION IS TO INSTALL A LOW VOLTAGE SYSTEM, PROVIDE |
| | DETAILS. IF THE INTENTION IS TO USE A 120 VOLT SYSTEM, |
| | REMOVE OR REVISE NOTE. FBC 107.2.1, R314, R315 |
| | 9. MASTER WIC SHOWS STANDARD RECESS LIGHTS. LIGHTING |
| | WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT |
| | LUMINAIRES OR LAMPHOLDERS SHALL NOT BE PERMITTED IN |
| | CLOTHES CLOSETS. PROVIDE CORRECTION. NEC 410.16(B), FBC |
| | RE4003.12 |
| | 10. A/C COMPRESSORS DISCONNECTS REQUIRE CLEARANCE PER |
| | NEC 110.26. CURRENT LOCATION FOR CU-2 AND POSSIBLY CU-3 |
| | DO NOT APPEAR TO CONFORM TO CODE. PROVIDE CORRECTION. A |
| | NOTE WILL SUFFICE. NEC 110.26; FBC RE3405.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |