Plan Review Notes
Plan Review Notes For Permit 17070457
Permit Number 17070457
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-28 09:08:15CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION SHOWS A "PANEL C". HOWEVER, THIS IS
 NOT SHOWN ON RISER DIAGRAM OR PLAN, AND THERE IS NO
 PANEL SCHEDULE FOR IT. PLEASE CLARIFY AND/OR CORRECT.
 FBC 107.2.1
 2. PANEL A, CIRCUITS 33,35 AND 34,36 SHOW #6 ROMEX ON A
 60 AMP BREAKER. #6 ROMEX WIRE IS NOT RATED FOR 60 AMPS.
 THERE IS NO MECHANICAL PLAN TO CONFIRM THE REQUIREMENTS
 OF THE UNITS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4; FBC 107.2.1, 107.3.5
 3. PANEL B, CIRCUIT 37,39 SHOW #6 ROMEX ON A 60 AMP
 BREAKER. #6 ROMEX WIRE IS NOT RATED FOR 60 AMPS. THERE
 IS NO MECHANICAL PLAN TO CONFIRM THE REQUIREMENTS OF
 THE UNITS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4; FBC 107.2.1, 107.3.5
 4. PROVIDE BLOCK NOTE THAT SEPARATE PERMITS WILL BE
 REQUIRED FOR POOL AND LOW VOLTAGE SYSTEMS. FBC 105.1
 5. PANEL P, CIRCUITS 1,3 AND 5,7 AND 6,8 AND POSSIBLY
 10 REQUIRE GFCI PROTECTION. WILL THESE BREAKERS BE
 INSTALLED UNDER THIS PERMIT IN PREPARATION FOR THE POOL
 UNDER SEPARATE PERMIT? IF NOT, PROVIDE NOTE THAT FUTURE
 INSTALLATION TO COMPLY. NEC 680.21(C), 680.44; FBC
 RE4203.1.3, RE4208.1; FBC 107.2.1
 6. NOTE # 19 STATES THAT CLOSET LIGHTING SHALL COMPLY
 WITH NEC 410.8, WHICH IS NOT THE CORRECT CODE SECTION
 FOR CLOSET LIGHTING. PROVIDE CORRECTION. NEC 410.16;
 FBC RE4003.12
 7. NOTE # 24 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 8. BLOCK NOTE ON SHEET A-3.1 STATES THAT IF THERE ARE
 MORE THAN 6 SMOKE DETECTORS, A LOW VOLTAGE SYSTEM
 SHOULD BE INSTALLED. THIS HOUSE HAS MORE THAN 6. IF THE
 INTENTION IS TO INSTALL A LOW VOLTAGE SYSTEM, PROVIDE
 DETAILS. IF THE INTENTION IS TO USE A 120 VOLT SYSTEM,
 REMOVE OR REVISE NOTE. FBC 107.2.1, R314, R315
 9. MASTER WIC SHOWS STANDARD RECESS LIGHTS. LIGHTING
 WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT
 LUMINAIRES OR LAMPHOLDERS SHALL NOT BE PERMITTED IN
 CLOTHES CLOSETS. PROVIDE CORRECTION. NEC 410.16(B), FBC
 RE4003.12
 10. A/C COMPRESSORS DISCONNECTS REQUIRE CLEARANCE PER
 NEC 110.26. CURRENT LOCATION FOR CU-2 AND POSSIBLY CU-3
 DO NOT APPEAR TO CONFORM TO CODE. PROVIDE CORRECTION. A
 NOTE WILL SUFFICE. NEC 110.26; FBC RE3405.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  