Plan Review Notes
Plan Review Notes For Permit 17070457
Permit Number 17070457
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-02 18:56:22NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONALS FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $561,478. THE
 PERMIT FEE BALANCE IS $9470.13.
  
 4- PLANS NEED TO SPECIFY ALL LOADS, INCLUDING THE ATTIC
 LIVE LOADS REQUIRED BY NOTES "B" AND "G" OF TABLE
 R301.5 FBC-RESIDENTIAL. SEE PLANS FOR AREAS WITH
 STORAGE. UPDATE STRUCTURAL NOTES ON SHEET S-D1.
  
 5- NEED TO SPECIFY CARBON MONOXIDE ALARM BY THE BEDROOM
 ON THE FIRST FLOOR AS REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL
 WITH COMPLETE SPECIFICATIONS FOR THE ANCHOR TYPE AND
 SPACING. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- RAILING NOTES ON SHEET A-2.1 ARE MISSING
 SPECIFICATIONS FOR THE LIVE LOAD REQUIREMENTS OF TABLE
 R301.5 FBC-RESIDENTIAL AND THE OPENINGS LIMITATIONS OF
 SEC. R31..1.3 FBC-RESIDENTIAL.
 NOTE: SHOP DRAWINGS REVIEWED/APPROVED BY THE DESIGNER
 OF RECORD WILL BE REQUIRED PRIOR TO INSTALLATION TO
 AVOID CONFLICTS/DELAYS.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS,
 INCLUDING ALL FRAMING MEMBERS AND CONNECTORS FOR THE
 CONSTRUCTION OF:
 A) METAL LOUVERS SHOWN ON THE EXTERIOR ELEVATIONS.
 B) METAL BAHAMA SHUTTERS SHOWN ON THE EXTERIOR
 ELEVATIONS.
 C) METAL COLONIAL SHUTTERS SHOWN ON THE EXTERIOR
 ELEVATIONS.
 D) ALUMINUM TRELLIS SHOWN ON THE EXTERIOR ELEVATIONS
 AND PLANS.
 E) FOUX WOOD OUTRIGGERS SHOWN ON EXTERIOR ELEVATIONS.
 F) DECORATIVE COMPOSITE WOOD BRACKETS SHOWN ON EXTERIOR
 ELEVATIONS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. IF SPECIFYING ROOF TILE
 ADHESIVE, THEN PRODUCT APPROVAL IS REQUIRED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES.
  
 10- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR THE
 ICYNENE SPRAY INSULATION SPECIFIED ON PLANS TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. NOTE:
 DESIGNER OF RECORD TO REVIEW/APPROVE REPORT PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  
 11- PROVIDE COMPLETE DETAIL/SECTION AND SPECIFICATIONS
 SHOWING THE 1 HR SOFFIT ASSEMBLY GA FILE NO RC 2602
 SPECIFIED ON SHEET A-7.
 TABLE R302.1(1) FBC-RESIDENTIAL.
  
 12- COLUMNS FOR ROOF ABOVE BALCONIES FOR BEDROOM #3 AND
 BEDROOM #4 ARE NOT CLEAR. CLEARLY SPECIFY COLUMNS. THEY
 ARE NOT IN THE COLUMN SCHEDULE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND
 DATE AT THE BOTTOM OF FORM AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) WALL ORIENTATION SHOWN DOESN'T MATCH WALL
 ORIENTATION SHOWN ON THE SITE PLAN. SEE SITE PLAN ON
 SHEET A-1. REVISE THE WALLS, AND WINDOWS INFORMATION TO
 MATCH THE ACTUAL ORIENTATION AS SHOWN ON PLANS. SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) REVISE THE ROOF TYPE AND AREA ON PAGE 2 OF 5 TO
 MATCH PLANS. THERE IS ONE AREA WITH A GABLE END. SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) DOORS INFORMATION ON PAGE 3 OF 5. SPECIFY THE
 "SPACE" WHERE THE WOOD DOOR IS LOCATED AT. "TWO STORY
 RES" IS NOT AN SPACE. REVISE AS REQUIRED. SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) WALLS INFORMATION. SPECIFY THE "SPACE" WHERE THE
 WALLS ARE LOCATED AT. "TWO STORY RES" IS NOT AN SPACE.
 REVISE AS REQUIRED. SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS IS
 REQUIRED WHEN THE CALCULATIONS ARE NOT USING THE
 DEFAULT FACTOR.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) OVERHEAD GARAGE DOOR AS SHOWN ON PLANS.
  
 B) MASTER BEDROOM SKYLIGHT AS SHOWN ON PLANS.
  
 C) FLAT ROOF AS SHOWN ON PLANS ABOVE SECOND FLOOR ROOF.
 NOTE: CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES.
  
 D) BALCONIES UNDERLAYMENT DESIGNED TO RECEIVE
 TILE/STONE AS SPECIFIED ON PLANS. NOTE: CLEARLY
 IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES.
  
 E) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOF TILE NOA FOR LISTED ADHESIVES.
  
 F) FRENCH DOORS NOA 15-0602.09 SUBMITTED: DRAWINGS
 SUBMITTED WITH THIS NOA ARE NOT LEGIBLE. THEY ARE CUT
 IN PIECES. PROVIDE COMPLETE AND LEGIBLE DRAWINGS.
  
 G) FIXED WINDOWS AS SHOWN ON PLANS.
  
 H) WINDOW AND DOOR MULLIONS AS SHOWN ON PLANS. AND
 SPECIFY MULLION SIZE FOR EACH APPLICATION TO VERIFY
 COMPLIANCE WITH THE DESIGN-PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
  
 I) FOLDING FRENCH DOOR AS SPECIFIED ON PLANS AT THE
 DINING AREA.
  
 J) CASEMENT WINDOWS AS SHOWN ON PLANS.
  
 K) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, WALL SECTIONS AND DETAILS. NOTE: PROVIDE ONLY
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR LIST THE FLORIDA
 PRODUCT APPROVAL NEXT TO EACH CONNECTOR.
  
 15- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 16- CLARIFY WHY SUBMITTING NOA 16-1108.04 FOR DYPLAST
 RIGID FOAM INSULATION. IF USING THIS PRODUCT, THEN
 REVISE ARCHITECTURAL PLANS SHOWING LOCATION OF THIS
 INSULATION. AND, DESIGNER OF RECORD TO REVIEW THIS NOA
 PRIOR TO SUBMITTAL TO THIS OFFICE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS.
  