Plan Review Notes
Plan Review Notes For Permit 17070450
Permit Number 17070450
Review Stop E
Sequence Number 2
Notes
Date Text
2017-10-25 14:12:21CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (COMMENTS NOT ADDRESSED ARE NOTED IN PARANTHESES).
  
 1. PROVIDE FLOOR PLAN FOR ENTIRE RESIDENCE, SHOWING
 LOCATION OF EXISTING SMOKE ALARMS. IF NONE ARE
 EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION.
 PROVIDE SMOKE ALARM IN THE IMMEDIATE VICINITY OUTSIDE
 THE NEW BEDROOM. FBC R314.3, R314.3.1; FBC 107.2.1
 (REPEAT COMMENT: NOT ADDRESSED)
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902 (REPEAT COMMENT: NOT ADDRESSED)
 3. PROVIDE LOAD CALCULATION TO CONFIRM EXISTING SERVICE
 IS ADEQUATE FOR THE ADDITIONAL LOAD. NEC 220; FBC
 RE3602.1 (REPEAT COMMENT: NOT ADDRESSED)
 4. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; FBC 107.2.1 (REPEAT COMMENT: NOT ADDRESSED)
 5. PROVIDE AFCI PROTECTION PER CODE: "ALL 120-VOLT,
 SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS
 SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION". NEC 210.12; FBC RE3902.12 (REPEAT COMMENT:
 NOT ADDRESSED)
 6. PROVIDE DEDICATED 20 AMP CIRCUIT FOR BATH GFCI
 OUTLET: "A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS".
 NEC 210.11(C)(3) , FBC RE3703.4 (REPEAT COMMENT: NOT
 ADDRESSED)
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 (REPEAT
 COMMENT: NOT ADDRESSED)
 8. PROVIDE RECEPTACLES PER THE NEC WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1
 (REPEAT COMMENT: NOT ADDRESSED)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  