| 2017-07-28 10:52:44 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE FLOOR PLAN FOR ENTIRE RESIDENCE, SHOWING |
| | LOCATION OF EXISTING SMOKE ALARMS. IF NONE ARE |
| | EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION. |
| | PROVIDE SMOKE ALARM IN THE IMMEDIATE VICINITY OUTSIDE |
| | THE NEW BEDROOM. FBC R314.3, R314.3.1; FBC 107.2.1 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC |
| | RE3706.2, RE3902 |
| | 3. PROVIDE LOAD CALCULATION TO CONFIRM EXISTING SERVICE |
| | IS ADEQUATE FOR THE ADDITIONAL LOAD. NEC 220; FBC |
| | RE3602.1 |
| | 4. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC |
| | 215.5; FBC 107.2.1 |
| | 5. PROVIDE AFCI PROTECTION PER CODE: "ALL 120-VOLT, |
| | SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS |
| | SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION". NEC 210.12; FBC RE3902.12 |
| | 6. PROVIDE DEDICATED 20 AMP CIRCUIT FOR BATH GFCI |
| | OUTLET: "A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT |
| | SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS". |
| | NEC 210.11(C)(3) , FBC RE3703.4 |
| | 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 8. PROVIDE RECEPTACLES PER THE NEC WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |