| 2017-08-08 18:22:34 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- PROPOSED EGRESS WINDOW DOESN'T COMPLY WITH THE |
| | EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. 5TH |
| | EDITION (2014). NEED TO COMPLY WITH THE MINIMUM WIDTH |
| | OPENING, MINIMUM HEIGHT OPENING AND MINIMUM TOTAL CLEAR |
| | OPENING. SEE SEC. R310 AND REVISE AS REQUIRED. |
| | |
| | 3- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | 4- PLANS NEED TO PROVIDE INFORMATION SHOWING COMPLIANCE |
| | WITH THE HEATING REQUIREMENTS OF SEC. R303.9 |
| | FBC-RESIDENTIAL. NOTE: PORTABLE HEATERS ARE NOT |
| | ALLOWED. |
| | |
| | 5- NEW BATHROOM WINDOW TO COMPLY WITH THE SAFETY |
| | GLAZING REQUIREMENTS OF SEC. R308.4.5 FBC-RESIDENTIAL |
| | IF THE WINDOW DOESN'T HAVE IMPACT GLASS. |
| | |
| | 6- PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW THE |
| | NEW CONCRETE BLOCK WALL IS ATTACHED TO THE EXISTING |
| | WOOD BEAM. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 7- WINDOW BUCK DETAIL: ENGINEER OF RECORD NEEDS TO |
| | SPECIFY ANCHOR TYPE AND SPACING FOR THE BUCK FASTENING. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 8- TYPICAL WALL SECTION: SPECIFY FOOTING REINFORCEMENT. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR; |
| | A) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | B) WINDOW MULLION AS SPECIFIED ON PLANS. AND, SPECIFY |
| | MULLION SIZE TO VERIFY COMPLIANCE WITH SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | C) ARCHED FIXED WINDOW AS SPECIFIED ON PLANS. |
| | |
| | D) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | E) HURRICANE SHUTTERS IF THE WINDOWS PRODUCT APPROVALS |
| | DON'T HAVE HURRICANE IMPACT GLASS. AND, PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| | |
| | 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR OWNER |
| | BUILDER) AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED |
| | BY SEC. 1098.3 CITY AMENDMENTS. REVISE VALUATION AS |
| | REQUIRED. |
| | |
| | *******ENGINER TO PROVIDE RESPONSE LETTER ADDRESING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |