2017-07-12 07:55:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. NOT ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE.
 PROVIDE ROOF PITCH, MEAN ROOF HEIGHT. SEE PAGE 5 OF THE
 METAL ROOF PRODUCT APPROVAL; TWO FASTENING OPTIONS ARE
 AVAILABLE. INDICATE WHICH IS PROPOSED (METHOD 1 OR
 METHOD 2).
 FBC 2014 RESIDENTIAL 301.2.
  
 DESIGN PRESSURES REQUIRED CANNOT BE DETERMINED WITHOUT
 PITCH AND ROOF HEIGHT INFORMATION. THIS MAY BE SENT VIA
 EMAIL AND DESIGN PRESSURES WILL BE DETERMINED FOR YOU.
 AFTER DESIGN PRESSURES ARE DETERMINED, APPLICANT CAN
 SELECT FASTENING METHOD. THIS ALSO WILL BE DONE FOR YOU
 UPON REQUEST.
  
  
  
  