| 2017-08-09 18:42:59 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MASTER BEDROOM DOES NOT HAVE ADEQUATE RETURN | | | AIR. THE TOTAL SUPPLY TO THE MASTER SUITE IS 350 CFMS | | | WHICH REQUIRES 175 SQUARE INCHES OF RETURN GRILL AREA. | | | ONLY 96 SQUARE INCHES IS PROVIDED. | | | | | | FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | | BEDROOMS. | | | 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF | | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN | | | UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE | | | REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS, | | | EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL | | | BE INCLUDED. |
|